Operation and maintenance of
IZM low voltage air circuit breakers
MOELLER
www.moeller.net/de/support
Figure 33. Top View Secondary Connectors
Figure 34. Secondary Connector Protective Hood
Drawout type circuit breakers
—Compatible secondary plug-in
connectors are mounted on the top front portion of the drawout
cassette (
). These connectors match and plug into the
circuit breaker mounted connectors. Contact points are wired from
the cassette’s plug-in connectors to cassette mounted terminal
blocks. The terminal blocks are also mounted on the top front
portion of the cassette. The secondary terminals have finger-proof
hinged covers with small holes for probe testing.
Secondary Connector Labels
Labels
Legend
OTS
Overcurrent Trip Switch
UVR
Undervoltage Release
ATR
Automatic Trip Relay (520M and 1150 trip units only)
INCOM
PowerNet Communications Network
A BUS
Future Use
A/S
Auxiliary Contacts
NEUTRAL Neutral Sensor Input
GF SGND Source Ground Input
ZONE
Zone Interlocking
ST
Shunt Trip
SR
Spring Release
MOTOR
Charging Motor
LCS
Latch Check Switch
Protective Hood
Fixed type circuit breakers
—There are two secondary
connection options:
1. Without terminal block
—If a terminal block for customer use
is not required, the circuit breaker is supplied with both plug-in
connectors (male and female) just described in the two previous
paragraphs. The plug-in connectors are joined and attached to
the top portion of the circuit breaker. The customer can plug
secondary wiring with crimp-on connectors into the back of the
plug-in connectors; subsequently the connections to the circuit
breaker can be quickly joined or separated as required.
2. With terminal block
—For those customers preferring to wire
to a terminal block, terminal blocks with finger-proof hinged
covers are added to the secondary configuration just described
for a fixed circuit breaker “without a terminal block.” The
terminal blocks are wired to the plug-in connectors and also
permanently attached to the upper rear portion of the
circuit breaker.
A standard tool is available from the plug-in connector manufacturer
(AMP) to facilitate the removal of secondary wiring from a plug-in
connector, or contact Moeller for assistance (
). The
connector halves must be separated to use this tool.
Connection diagrams
The connection diagrams for all IZM circuit breakers using Digitrip
RMS trip units are shown in
through
Figure 35. Cassette-Mounted Secondary Wiring
Figure 36. AMP Secondary Wiring Removal Tool
Terminal Blocks
Closed Hinged Covers
with Testing Holes