To attach the drive (short rod) end of a cable to the drive lever push 

swivel fitting (refer to 

Figure 11

), follow the directions below (see 

Figure 12

) .

1 .  Remove upper nut from end of rod of cable assembly .
2 .  Slide rubber boot toward tip of rod .
3 .  Unthread outer bulkhead nut and slide nut and lock washer 

toward tip .

4 .  Insert threaded end of rod with 38,1 mm (1,5 inch) tube spacer 

into swivel fitting, ensuring that the compression spring remains 

between the lower nuts and the swivel .

5 .  Slide smaller diameter portion of bulkhead fitting into cable 

 bracket slot, keeping one of the two lock washers with each 

 bulkhead  nut .

6 .  Raise the cable assembly until threaded portion of bulkhead fit-

ting enters slotted hole in cable bracket (threads show  

above bracket) .

7 .  Bring bulkhead washer and nut down to threads and hand 

 tighten .

8 .  Adjust two bulkhead nuts to approximately center the threaded 

section of the bulkhead fitting on the cable mounting bracket . 

9 .  Hand tighten the bulkhead nuts at this time .
10 . Slide rubber boot back into place over end of bulkhead fitting .
11 . Lower nuts should be against the stop at the end of thread and 

upper nut tightened against tube spacer .

12 . Hold lower nuts and torque upper nut to 3,3–4,5 N·m  

(30–40 in-lb) .

Step 8

This step describes how to attach the driven (long rod) end of a 

cable attached to an interlock assembly on another breaker to the 

cable bracket and interlock assembly on this IZM breaker . Refer to 

Figure 10

 and 

Figure 11

 for cable routing and correct swivel fittings 

to which the cables are connected . 
The driven (long rod) end of the cable is attached to the correspond-

ing push or pull swivel fitting on the driven lever on this cable inter-

lock assembly similarly to 

Step 7

 except the driven end does not 

utilize a compression spring between the swivel and nut . For the 

push cable, remove and discard the 22,2 mm (0,875 inch) cable tube 

spacer 

(P)

 on the rod end of the cable assembly 

(N)

 and replace it 

with the 38,1 mm (1,5 inch) cable tube spacer 

(O)

 . For the pull cable, 

remove and discard the 22,2 mm (0,875 inch) cable tube spacer 

(P) 

on the rod end of the cable assembly 

(N) 

and replace it with the 

41,3 mm (1,625 inch) cable tube spacer 

(M)

 . Install as shown in 

Figure 17

 .

Step 9

This step describes how to adjust the cables to ensure proper 

 functionality of the cable interlock setup . Cable adjustments are 

made with the large bulkhead nuts 

ONLY

 and with all breakers 

OPEN

 . Nuts on the rod ends should not be moved . 

Begin by adjusting or verifying that the threaded section of all 

 bulkhead fittings are approximately centered on the cable mounting 

brackets, allowing for room to adjust in either direction . Hand tighten 

the nuts at this time .
Perform initial adjustments on the driven (long rod) end of cable  

until the gaps identified in 

Figure 13

 through 

Figure 16

 are as 

 specified . 

Figure 13

 through 

Figure 16

 show the position of the 

interlock assembly driven “And” lever based on the state of the 

interconnected breakers .

Gap 

0 mm

Connected 

breaker open

Connected 

breaker open

Gap 

0–10 mm

Figure 13. Driven “And” lever position with interconnected 

breakers open

Figure 14. Driven “And” lever position with interconnected push 

breaker open and pull breaker closed

Figure 15. Driven “And” lever position with interconnected push 

breaker closed and pull breaker open

Gap 

0–4 mm

Connected 

breaker open

Gap 

0 mm

Connected 

breaker closed

Gap 

0–4 mm

Connected 

breaker closed

Connected 

breaker open

Содержание IZM Series

Страница 1: ...d removal instructions for IZM series fixed breaker three way Type 32 cable interlock kit Contents Description Page General information 2 Installation of cable interlock assembly 4 Functional test of...

Страница 2: ...talling and interconnecting one fixed IZM breaker to another type of low voltage circuit breaker LVCB in any position see A B C in Table 1 for a Type 32 interlock configuration as shown in Figure 1 Wh...

Страница 3: ...IL CAB3050 1 a Cable kits are purchased separately as needed Figure 2 Interlock kit part identification includes parts to install on a single fixed IZM frame breaker and cassette does not include cabl...

Страница 4: ...ch and a small hammer to carefully punch out the window Once the window is removed use a small file to remove any burrs that remain Make certain that all pieces and or particles are cleaned up and rem...

Страница 5: ...to which the open slots in the top of the mounting plate will slide Now insert the mounting bracket slots onto the upper bolts and rotate the bracket down against the side of the breaker Make sure tha...

Страница 6: ...THE CABLES WILL BE ATTACHED IN DIFFERENT LOCATIONS THE CABLE MOUNTING ON BOTH POINTS OF THE DRIVE AND DRIVEN LEVERS ARE DESCRIBED BELOW TABLE 4 SHOWS THE TYPE 32 INTERLOCK LOGIC DEPENDING ON POSITION...

Страница 7: ...nter the threaded section of the bulkhead fitting on the cable mounting bracket 9 Hand tighten the bulkhead nuts at this time 10 Slide rubber boot back into place over end of bulkhead fitting 11 Repla...

Страница 8: ...the cables are connected The driven long rod end of the cable is attached to the correspond ing push or pull swivel fitting on the driven lever on this cable inter lock assembly similarly to Step 7 ex...

Страница 9: ...ts to 11 13 N m 100 120 in lb without mov ing the bulkhead fittings After the driven end has been adjusted and the bulkhead nuts have been tightened perform adjustments on the drive short rod end of t...

Страница 10: ...d able to CLOSE one at a time OPEN Breaker C CHARGE and CLOSE Breakers A and B Breaker C should be interlocked held OPEN not able to CLOSE CHARGE and attempt to CLOSE Breaker C it should not respond t...

Страница 11: ...11 Instructional Leaflet IL0131187EN Effective June 2022 Installation and removal instructions for IZM series fixed breaker three wayType 32 cable interlock kit EATON www eaton com...

Страница 12: ...ng policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPO...

Отзывы: