EMP DESCRIPTION AND FEATURES

The optional Environmental Monitoring Probe (EMP) enables you to collect temperature 
and humidity readings in the rack environment and monitor the environmental data remotely. 
You can also collect and retrieve the status of two contact devices (user-provided).
The EMP device is delivered with a screw and screw anchor, velcro fasteners, tie wraps, 
and a connection cable. You can install the device anywhere on the rack.

The EMP has the following features:

•  The hot-swap feature simplifies installation by enabling you to install the probe safely 

without turning off the IPC3000 power or the loads that are connected to it.

• 

The EMP monitors temperature and humidity information to help you protect critical 
equipment:

-  The EMP measures temperatures from 0°C to 70°C with an accuracy of ±2°C.
-  The EMP measures relative humidity from 10% to 90% with an accuracy of ±5%.

• 

The EMP can be located some distance away from the IPC3000 with a CAT5 network 
cable up to 20 m (65.6 ft) long.

• 

The EMP monitors the status of the two user-provided contact devices.

For more information, refer to the Intelligent Power Controller 

TM

 3000 (IPC3000) User 

Manual. View it online at:

CONNECT AN EXTERNAL CONTACT DEVICE TO THE EMP :

To connect an external device to the EMP:
1.  Connect the external contact closure inputs to the terminal block on the EMP (see the 

table and the figure below):

External contact device 1

. Connect the return and signal input wires from  

device 1 to screw terminals 1 and 2.

External contact device 2

. Connect the return and signal input wires from  

device 2 to screw terminals 3 and 4.

2.  Tighten the corresponding tightening screws on top of the EMP to secure the wires.

NOTE

: External contact devices can be normally open (NO) or normally closed (NC).

EMP setup

Device

Terminal 

Number

Normally Open or Normally Closed

External Contact Device 1 

Connection

1

Contact 1 Return 

Normally Closed

2

Contact 1 Signal Inputs Normally Open

External Contact Device 2 

Connection

3

Contact 2 Return

Normally Closed

4

Contact 2 Signal Inputs Normally Open

1

2

4

1 2 3

External Contact Device 1

External Contact Device 2