background image

Installation 

i-on160EX 

Page 26 

seconds while the control unit scans the bus. 
When the control unit has finished scanning 
the bus the keypads show: 





2.  Press and hold keys A and 

 simultaneously 

on the keypad that you wish to use for initial 
programming. 

NOTE: Hold the keys down 

for at least three seconds.

 

After a short pause the keypad gives a 
confirmation tone. The display briefly shows 
the bus address of the keypad. If there are no 
other keypads connected to the bus it should 
be “b1-d51”(bus 1 device 51). Keypads take 
bus device addresses 51 upwards. 

(If you are installing a UK control unit please 
go to step 6.) 

On an EUR control unit the keypad display 
then shows: 





3.  Press 

 or 

 followed by 

 to select the 

language you want. 

From this point on, the display operates in the 
selected language. If you want to change the 
language later use 

Installer Menu - System 

Options - Language

.

 

The display shows: 





4.  Press 

 or 

 to show other countries, for 

example 





5.  Press 

 to select the country you wish to use. 

The display shows: 





6.  Press A or B to select either a Partitioned 

system or a Part Setting system. 

Note: To change between a partition and a part 
setting system at a later date will require a factory 
default. 

The display shows: 





7.  EITHER Press 

 if there is NO battery 

connected to BATT2 (see 15 in Figure 3). 

 

OR press 

 followed by 

 if you have 

connected a battery to the BATT2 terminals 
and wish to enable fault reporting on battery 
2. 

The display shows: 





8.  Press 

 or 

 to show the Security Grades 

available, for example: 





9.  Press 

 to select the security grade you 

intend to use for the system. 

The display shows: 





10. Press 

 or 

 to show the range of zone 

wiring types available, for example: 





11. Press 

 to select the wiring type you intend to 

use for the wired zones. 

Note: This initial choice fixes the wiring type for 
the control unit and any attached wired 
expanders. If you wish to use a different wiring 
type on the expanders then use 

Installer Menu 

– 

Detectors/Devices 

– Wired Expander

 after the 

initial power up to change the wiring type for each 
expander. 

If the control unit lid is open then the display 
shows: 





Note that the alert LEDs round the navigation 
key glow red. This is because the control unit 
lid is off and the tamper is active.  

12. Press 

The display shows: 





13. Press 

The display shows: 





14. Press 

The display shows: 





15. Press 

.  

The display shows: 





At this point you must make the control unit 
allocate an address to each of the connected 
bus devices, as follows: 

16. Go to each bus device. You can visit the 

devices in any order, but if you visit them in 
the order you want their address numbers to 
appear then it will make subsequent 
programming easier. The control unit assigns 
the next free bus address to a bus device 
when you make the device request a bus 
address.  

For keypads: 

 

Hold down keys A and 

 until the display 

shows a bus and device number. For 

Содержание i-on160EX

Страница 1: ...i on160EX Security System Installation Guide Issue 9...

Страница 2: ...quipment but will not damage the equipment Caution Describes actions that will physically damage the equipment and prevent its proper function WARNING Describes actions that are hazardous to health or...

Страница 3: ...Cabling 19 Step 6 Connect Wired Zones 20 Four Wire Closed Circuit Connections 20 Two Wire Closed Circuit Connections 20 Fully Supervised Loop Connections 20 Shock Sensors and Roller Shutter Sensors 22...

Страница 4: ...i on160EX Page iv This page is intentionally blank...

Страница 5: ...sed as part of a Security Grade 3 system The control unit is also approved to operate as part of a Security Grade 2 system If you install any radio devices this will limit approval to Security Grade 2...

Страница 6: ...or laptop connected to the Ethernet port on the control unit PCB The control unit contains a web page server and you can use any web browser to see a complete version of the Installer menu Please see...

Страница 7: ...tion can all affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtainable from www coopersecurity co uk for...

Страница 8: ...tal or conducting films These glasses are particularly poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the i on160EX its expanders and keypads have been tested for...

Страница 9: ...tors 11 RS485 terminator 12 Engineering keypad connector 13 Zone output Aux power and Bus connectors 14 Kickstart pins Batt 1 only 15 Battery connectors two of 16 20Vac connector 17 USB socket Mini B...

Страница 10: ...ixed To open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the keypad rear hou...

Страница 11: ...e bottom edge of the caps in with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 9 Gently swing the lower side of the front out from the back box by ab...

Страница 12: ...amper switch 2 Sounder 3 Connector for KEY EP Terminals for zones 4 Sounder volume control 5 Connector for control unit bus and output terminal 6 Jumpers for 6a Addressing not used in i onEX control u...

Страница 13: ...er connectors 19 Outputs Figure 15 EXP W10 Wired Expander 1 Cable entry also behind PCB 2 Central keyhole 3 PCB 4 Relay card i rc01 connector 5 Aux power 6 Link to enable disable front rear tamper swi...

Страница 14: ...able front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connector 11 Bus cable connector 12 Sounder 13 Louds...

Страница 15: ...and would meet the EN50131 1 Grade 3 requirements A single new fully charged charged 17A battery can provide the charge required by the example system for PD6662 Grade 3 requirements Note All current...

Страница 16: ...only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 18 If required fit the termination jumper at the devices on the end of each arm If there are...

Страница 17: ...4 03V 4 61V 5 18V 5 76V 380mA 0 61V 1 22V 1 82V 2 43V 3 04V 3 65V 4 26V 4 86V 5 47V 6 08V 400mA 0 64V 1 28V 1 92V 2 56V 3 20V 3 84V 4 48V 5 12V 5 76V 6 40V Reducing Voltage Drop Method 1 Double up th...

Страница 18: ...k the position of the case Also mark the position where the lid back tamper bracket touches the wall There must be enough space around this point to fit the supplied tamper shroud see Figure 21 Fittin...

Страница 19: ...s the KEY EP or prox readers used by other systems for example access control systems If you mount prox readers closer together than one meter including on the other side of walls then the two prox re...

Страница 20: ...lights by fitting links over the BRIGHT jumper on the keypad pcb see 1b in Figure 12 or 6b in Figure 14 Jumper OFF The keypad backlights glow at normal intensity Jumper ON The keypad backlights glow e...

Страница 21: ...al programming mode and save your changes see below To Disable Enable the Status OK LED 1 Enter Local Programming mode MENU ABCD 2 Press repeatedly until the display shows MENU STATUS OK LED 3 Press r...

Страница 22: ...ou do so then the prox readers will interfere and be unable to read tags Opening the External Prox Reader To open the external prox reader see Figure 27 1 Undo the single retaining screw 2 Tilt the ed...

Страница 23: ...Expanders Addressing Expanders The control unit assigns addresses to all devices connected to the bus cable You can start this process off from the Installer Menu during the initial power up See Initi...

Страница 24: ...wiring for CCL zones on the KEY KPZ01 Figure 35 KEY KPZ01 CCL Zone Wiring Two Wire Closed Circuit Connections With version 4 02 and higher software you can connect two wire CCL detectors to each pair...

Страница 25: ...xamples Figure 39 Wiring FSL Zones on KEY KPZ01 When programming select the FSL resistor values for the control unit in Installer Menu System Options Wired Zone Type To select the resistor values for...

Страница 26: ...istors and are capable of sinking a maximum 500mA when active By default outputs 3 and 4 are 0V when active 12V when inactive If you wish to reverse the polarity of these two outputs see Changing the...

Страница 27: ...the alarm contacts only and link the tamper contacts together with a short length of wire In the Installer Menu program the zone with a type of Tamper Program the outputs used to trigger the siren and...

Страница 28: ...pes See the i on Range Engineering Guide for details on how to change the defaults Figure 48 Plug By Communicator Wiring Note Comms O P4 will be active when the system is unset This is normal To fit a...

Страница 29: ...connector The control unit will generate an ATE L F Single alert if only one of the networks is not available or ATE L F All if both networks are not available Step 9 Fit and Connect Battery Fit eithe...

Страница 30: ...you have connected a battery to the BATT2 terminals and wish to enable fault reporting on battery 2 The display shows 8 Press or to show the Security Grades available for example 9 Press to select the...

Страница 31: ...briefly display the message Installer session transferred for 5 seconds before reverting to the time and date Leaving the Installer Menu If you wish to leave the Installer Menu at any time 1 Press un...

Страница 32: ...ion complies with BS8243 only if the user has given written consent 3 If you key in an access code incorrectly the display shows four stars Key in the code again If you key in a total of four incorrec...

Страница 33: ...to select the desired mode The display shows 6 Press or to display the desired Security Grade 2 or 3 on the bottom line of the display and then press to select it The display shows 7 Press or to displ...

Страница 34: ...make sure that you allocate keypads correctly to partitions For more information see Assigning Wired Keypads to Partitions in the i on Range Engineering Guide Assemble and close the control unit a Fit...

Страница 35: ...OPTIONS Wired Zone type Panel Zones All Zones User Access HUA keys active Quick set Quick omit User code reqd 2 Way Replies 2w Set Instant Duress Enable User reset Zone alarms 6 Zone tampers System t...

Страница 36: ...17 Appears only when Dynamic Test call disabled 18 Appears only if EXP PSU is fitted 19 Appears only when Report Type Fast Format AND Confirmation Mode Basic 20 Shows None if no module fitted 21 Must...

Страница 37: ...if you wish to find the location of any keypad or expander you can employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone...

Страница 38: ...ts 1 500 mandatory events 500 non mandatory Stored in EEPROM memory available for at least 10 years without power Internal Clock 10 minutes over one year depending on the accuracy of the mains supply...

Страница 39: ...65mA backlight high KEY KPZ01 KP01 K01 power requirement 35mA backlight OFF internal prox reader only 65mA max backlight ON external prox reader connected Wired Expander requirement 20mA max quiescent...

Страница 40: ...Grade 2 The i sd02 is compliant with EN50136 1 as an ATS2 communicator The i sd02 may be used as a supplementary communicator at Grade 3 At Grade 2 the i sd02 provides a compliant communicator for th...

Страница 41: ...i fb01 Four button remote control 727rEUR 00 Four button remote control with encrypted code HUD function not compatible with BS8243 or DD243 Communicators i dig02 PSTN Communication ARC only i gsm02 G...

Страница 42: ...i on160EX Page 38 This page is intentionally blank...

Страница 43: ...i on160EX Page 39 This page is intentionally blank...

Страница 44: ...www coopersecurity co uk Product Support UK Tel 44 0 1594 541978 Available between 08 30 to 17 00 Monday to Friday Product Support Fax 01594 545401 email techsupport coopersecurity co uk Part Number...

Отзывы: