background image

Put the number 1 base plate to its place and 
mount it to the switchgear.

Connect the cable holder to L1 phase. Connect 
the earthing head to the ground earthing.

Replace the bellows on the cable.

Put the number 2 base plate to its place and 
mount it to the switchgear. Assemble the cable 
clamp. Connect the cable earthing to the busbar 
earthing. 

Repeat these operations again for L2 and L3 
phases.

Prepare the cable termination.

Installation  of Toroid Transformers:

If Toroid transformers will be used in the 
switchgears, transformers are prepared 
seperately, mounted to the cables and fixed.

Installation of MV Cables

Ulusoy HMH36 Metal Enclosed Modular Switchgear User Manual

   June 2020 www.eaton.com

Содержание HMH36

Страница 1: ...Ulusoy HMH36 Metal Enclosed Modular Switchgear User Manual www eaton com...

Страница 2: ...PREPARING THE SWITCHGEARS FOR INSTALLATION 2 INSTALLATION INSTRUCTIONS 3 INSTALLATION OF SWITCHGEARS INSIDE A BUILDING 4 GROUND GRADIENT TOLERANCE 5 INSTALLATION OF MAIN BUSBAR 6 INSTALLATION OF EART...

Страница 3: ...Forklift Transportation with Sling Transportation on Pipes Roll on the pipes Carry with palette Max 90 Remove the bolts which mounts the switchgear to the palette Ulusoy HMH36 Metal Enclosed Modular S...

Страница 4: ...lts which mounts the switchgear to the palette Disassemble the top sheet metal Disassemble the lifting plates Pull out the front cover of the switchgear f N Storage Instructions 2 Ulusoy HMH36 Metal E...

Страница 5: ...zes for Fixing Type A mm B mm HMH 36 01 750 628 HMH 36 02 750 628 HMH 36 03 750 628 HMH 36 04 1000 878 HMH 36 05 1500 1378 HMH 36 06 750 628 HMH 36 07 750 628 HMH 36 08 1000 878 HMH 36 09 750 628 HMH...

Страница 6: ...hgear M f N M Installation of Switchgears Inside a Building nden g r n kablo GAUS S HMH 36 0 I I 0 GAUS S HMH 36 I 0 1 0 GAUS S HMH 36 I 0 1 0 Cable canal Wall nden g r n kablo GAUS S HMH 36 0 I I 0 G...

Страница 7: ...150 630 665 1x185 650 680 1x240 690 720 Single Core Cables Width a max b max 750 mm 3 6 1000 mm 4 6 1500 mm 7 6 Sizes in mm The ground gradients should not exceed the values given on the chart for the...

Страница 8: ...ert busbars and spheres between separator insulators of second switchgear and separator insulators of third switchgear and tighten the separator insulator busbar bolts through the sphere with a torque...

Страница 9: ...sheet metal Installation of Earthing Busbar f M A A view C B B C D D view view view view 1 Main Busbars 2 Liaison Busbars 3 M8x20 Bolt Ulusoy HMH36 Metal Enclosed Modular Switchgear User Manual June...

Страница 10: ...to the switchgear Assemble the cable clamp Connect the cable earthing to the busbar earthing Repeat these operations again for L2 and L3 phases Prepare the cable termination Installation of Toroid Tra...

Страница 11: ...3 terminal and cable to number 4 terminal in X1terminal series In transformer protection switchgears connect the Buccholz cables and transformer protection cables to the related terminals M f M M f N...

Страница 12: ...is to improve the quality of life and the environment through the use of power management technologies and services We provide sustainable solutions that help our customers effectively manage electric...