Explosion-protected safety switch 10A,  
GHG 261

The properly bared conductors of cables shall 
be connected with due regard to the respective 
regulations.

To maintain the explosion protection, conduc-
tors shall be connected with special care.

The insulation shall reach up to the terminal. 
The conductor itself shall not be damaged.

The minimum and maximum conductor cross 
sections that can be connected shall be 
observed (see technical data).

All screws and / or nuts of connection 
terminals, including those not in use, shall be 
tightened down securely.

Excessive tightening may affect or damage 
the connection.

The standard terminals are designed for the 
direct connection of conductors with copper 
wires. 

If multi- or fine-wire connection cables are 
used, the wire ends shall be handled according 
to the applicable national and international regu-
lations (e.g. use of multicore cable ends).

The position of the connection terminals is 
shown in the wiring diagrams on the switch 
base and in fig. 3 on page 7 of the operating 
instructions. 

To ensure that the safety switch closes 
correctly, switching at the switch shaft of the 
switch insert is not permitted when the 
apparatus is open.

If, to facilitate the feeding of conductors into 
the enclosure, the switch insert is removed 
from the enclosure base, it shall be put back 
correctly  before the electrical connection is 
made. 

6.3  Cable entries (KLE);  
 

blanking plugs

Generally only certified cable entries and 
blanking plugs may be used.

Flexible cables shall be used with trumpet-
shaped cable glands or other suitable 
entries with additional pull relief.

When using cable entries with a degree of 
protection that is lower than the IP protection 
of the apparatus (see page 6), the degree of IP 
protection for the complete unit is reduced.

The relevant mounting directives for cables 
entries being used shall be observed.

In order to ensure the minimum degree of 
protection, any unused entry holes shall be 
sealed with certified blanking plugs.

When fitting cable entries, care has to be taken 
that the sealing inserts are suitable for the 
cable diameter. In the case of sealing inserts 
that are cut out, it is necessary to ensure that 
the insert is properly adapted to the cable  
diameter.

In order to ensure the required minimum 
degree of protection, the cable entries shall be 
tightened down securely.

Overtightening can impair the degree of 
protection.

Warning: When tightening the cap nut of the 
metal cable entry (e.g. type ADL/ADE),a 
suitable tool shall be used to safeguard  the 
gland against twisting.

Any unused metric CEAG cable entries shall be 
sealed with the blanking plug certified for these 
metric cable entries.

6.4  Metal plates and  

 

 

 

external earth connection

In case an external earth connection is 
mounted on the plastic enclosure, it should be 
connected with a max. 25mm² wire.

This earth connection is inserted through a M6 
drill in the inner wall of the enclosure (see fig. 4). 
The standard terminals are designed for the 
direct connection of conductors with copper 
wires. 

Warning: Metal plates and metal glands 
shall be incorporated  in the potential equali-
zation.

6.5  Closing apparatus

Any foreign matter shall be removed from 
the apparatus.

The switch handle on the cover of the switch is 
to be set to the "ON" position.

When fitting the apparatus cover, care shall 
be taken to ensure that the switch shaft of 
the switch insert engages correctly in the 
carrier hole of the switch handle.

To ensure the required minimum degree of 
protection, the cover screws shall be tightened 
down.

Overtightening may impair the degree of 
protection.

6.6  Putting into operation

Before putting the apparatus into operation, the 
tests specified in the individual national 
regulations shall be performed. 

In addition to this, before being put into 
operation, the correct functioning of the 
apparatus and installation of the apparatus shall 
be checked in accordance with these operating 
instructions and other applicable regulations.

The improper operation of safety switches 
may result in the invalidation of the 
guarantee.

Maintenance / Servicing

The valid national regulations for the 
servicing / maintenance of electrical 
apparatus for use in potentially explosive 
atmospheres shall be observed  
(IEC/EN 60079-17).

Prior to opening the enclosure, it is 
necessary to ensure that the voltage supply 
has been isolated or to take suitable 
protective measures.

The necessary intervals between servicing 
depend upon the specific application and shall 
be stipulated by the operator according to the 
respective operating conditions.

During servicing, special attention shall be 
given to checking the parts on which the 
explosion protection depends (e.g. intactness 
of the flameproof components, the enclosure, 
the seals and cable entries).

If, in the course of servicing, it is ascertained, 
that repairs are necessary, section 8 of these 
operating instructions shall be observed.

Repairs / Overhaul / 

 Modifications

Only original COOPER Crouse-Hinds  parts 
shall be used for carrying out repairs.

In the event of damage to the flameproof 
encapsulation,  replacement of these 
components is mandatory. In case of doubt, 
the respective apparatus shall be sent to 
COOPER Crouse-Hinds for repair.

Repairs that affect the explosion protection 
may only be carried out by COOPER 
Crouse-Hinds  or by a qualified electrician in 
compliance with the respective national 
regulations (IEC/EN 60079-19).

Modifications or changes to the safety 
switches are not permitted.

Disposal / Recycling

The respective valid national regulations for 
waste disposal shall be observed when 
disposing of apparatus.

To facilitate the recycling of individual parts, 
parts made of moulded plastic shall bear the 
marking for the type of plastic used.

The product range is subject to changes and 
additions.

 External earth connection

Inner wall of 

the enclosure

 Fig. 4

Internal  

earth plate 

Internal earth  

connection