Section 1: System installation and design
Installation
The panel should be installed in a clean, dry, reasonably well ventilated place, and
not in direct sunlight . Temperatures in excess of +45°C and below -10°C may cause
problems, if in doubt consult Technical Support . The panel should be located away
from any potential hazard, in a position where it is readily accessible to authorised
staff, and the fire services, ideally on the perimeter of a building near a permanent
entrance . Mount the panel to the wall using the drill template provided . Do not drill
through the panel to the wall as dust will contaminate the circuitry .
Installation guide
1.
Never carry out insulation tests on cables connected to electronic equipment .
2.
DO NOT OVER TIGHTEN TERMINAL CONNECTOR SCREWS
3.
Always use the correct type of cables specifically designed for the operation of
fire detection and alarm circuits .
4.
Always adhere to volt drop limitation when sizing cables
5.
Always observe polarity throughout . Non colour coded conductors should be
permanently identified .
6.
Screen continuity must be maintained throughout the entire loop circuit including
at each junction point and at each device, terminals are provided on each device
to facilitate this .
7.
The screen should be earthed at the connection point provided at the Panel and
not at any other point . Both the loop start and the loop end must be connected to
the appropriate earthing points .
Care must be taken to avoid connecting the screen to the earthed body of any metal
devices, enclosures or cable containment . The screen or drain wire of the loop cables
should not be considered as safety earth and therefore should not be connected
to terminals marked with the earth symbol, except at the panel, and should not be
insulated with green and yellow sleeving .
8.
The Panel utilises intelligent soft addressing technology to greatly simplify
the installation and commissioning processes . Once the system has been
installed and the autolearn menu selected, the control panel will automatically
scan the detection loops and allocate each device with an address number
corresponding with its position on the loop, this avoids the traditional need for
manual addressing of the system devices which is time consuming and provides
a potential for error .