Expanding inputs/outputs
For more information visit:
www.EatonElectrical.com
MN05013005E
81
Remote expansion
Remote expansion units can be installed and run up to 30 m
away from the basic unit.
Figure 63: Connecting remote expansion units to the EZD
Warning!
The two-wire or multiple-wire cable between the devices
must adhere to the insulation voltage requirement which is
stipulated for the installation environment. Otherwise, a
fault (ground fault, short-circuit) may lead to the destruction
of the units or injury to persons.
A cable such as NYM-0 with a rated operational voltage of
U
e
= 300/500 V AC is normally sufficient.
E+ E–
E+ E–
EZD-CP..
EZ6..RE/TE
U
e
= 300/500 V
EZ200-
J
Terminals E+ and E– of the EZ200-EZ are protected
against short-circuits and polarity reversal.
Functionality is only ensured if E+ is connected with E+ and
E- with E-.