Mounting the display/operating unit, “front mounting”
Figure 11: Drill holes for the EZD
X
Drill and punch out two 22.5 mm diameter holes. The
diameter is the same as is normally required for control
circuit devices.
30
22.5
J
Observe the following technical requirements:
• The hole spacing is 30 mm.
• The maximum thickness of the front plate for mounting
the power supply/CPU module must not be more than
6 mm.
• The maximum thickness of the front plate for mounting an
expansion unit with a top-hat rail in addition to the power
supply/CPU module must not be more than 4 mm.
• Leave enough space at the side for the power supply/
CPU module, and if necessary, the expansion unit.
• In order to ensure protection to IP65, the surface of the
mounting front must be even and smooth.