For more information visit:
www.EatonElectrical.com
Programming wiring
MN05013005E
208
7: accept preset actual value, coil CI..EN
8: reset coil CI..RE
9: contact (make contact) CI..OF upper setpoint value reached,
exceeded
10: contact (make contact) CI..FB lower setpoint value reached,
undershot
11: contact (make contact) CI..ZE actual value equal to zero
12: contact (make contact) CI..CY value range exceeded
or undershot
• Range A:
– The counter counts upwards.
– The value leaves the lower threshold value and reaches the
upper value.
• Range B:
– The count direction changes to a downward count.
– The contacts switch in accordance with the actual value.
• Range C:
– The enable signal is set to 0. The actual value becomes 0.
• Range D:
– The rising edge on the accept preset value coil sets the actual
value to the preset value.
• Range E:
– The reset pulse sets the actual value to zero.
• Range F:
– The actual value goes outside the value range of the counter.
– The contacts become active according to the direction of the
values (positive or negative).
Comparators
Comparator function blocks allow you to compare constants
and variables with one another.
The following comparisons are possible:
Function block input
Function block input
>I1
Greater than
>I2
Equal to
Less than