14 Technical data
20
ESR5-VE3-42
07/20 MN049003EN
www.eaton.com
Technical safety data
Stop category according to IEC 60204
1
Safety parameters for IEC 61508 - High demand
SIL
3 (in conjunction with suitable evaluating device)
PFH
d
1.35 x 10
-9
per hour
Requirement rate
< 12 months
Proof test interval
240 months
Duration of use
240 months
The specifications apply assuming the following calculation basis:
B
10d
300000 (at 5
A DC-13)
Cycles
8760 per year
Safety parameters for IEC 61508 - Low demand
SIL
3 (in conjunction with suitable evaluating device)
PFD
avg
1.49 x 10
-4
Proof test interval
67 months
Duration of use
240 months
Safety characteristic data according to EN ISO 13849
Category
3 (in conjunction with suitable evaluating device)
Performance Level
e (in conjunction with suitable evaluating device)
Duration of use
240 months
For applications in PL e, the required demand rate for the safety function is once per month.
The specifications apply assuming the following calculation basis:
B
10d
300000 (at 5
A DC-13)
Cycles
8760 per year
Safety parameters for EN 62061
SIL CL
3 (in conjunction with suitable evaluating device)
For SIL CL 3 applications the required demand rate for the safety function is once per month..