![Eaton ESR5-NO-31-UC Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/eaton/esr5-no-31-uc/esr5-no-31-uc_manual_4014045015.webp)
Manual ESR5-NO-31-UC
07/2017 MN049014 EN www.eaton.com
11
With the manual, monitored reset device, a machine start may not be trigge-
red in accordance with EN ISO 13849-1.
Inductive loads can lead to welded relay contacts.
•
Connect a suitable and effective protective circuit to inductive loads.
•
Implement the protective circuit parallel to the load and not parallel to
the switch contact.
Magnetic fields can influence the device. The magnetic field strength of the
environment must not exceed 30 A/m.
•
Do not use the device in the vicinity of strong magnetic fields
(e.g., caused by transformers or magnetic iron).
Noise emission may occur when operating relay modules. Wireless recep-
tion may be disrupted in residential areas.
The device is a Class A product.
•
Observe the requirements for noise emission for electrical and electro-
nic equipment (EN 61000-6-4).
•
Implement appropriate precautions against noise emission.
Faulty devices
The devices may be damaged following an error. Correct operation can no
longer be ensured.
•
In the event of an error, replace the device.
Only the manufacturer or their authorized representative may perform the
following activities. Otherwise the warranty is invalidated.
•
Repairs to the device
•
Opening the housing
Taking out of service and disposal
•
Dispose of the device in accordance with environmental regulations.
•
Make sure that the device can never be reused.