13 Application example
13.1 Two-channel emergency stop monitoring with contact extension
•
Manual, monitored start
•
Monitoring of external contactors
•
Suitable up to category
4, PL e (EN
ISO
13849-1),
SIL
3 (EN
62061), if cross-circuits can be ruled out in the control for
contact extension
Figure 11: Two-channel emergency stop monitoring with contact extension
S1 - Emergency stop button
K3, …, K8 - Contactors
→
Cross-circuits in the cable installation can be excluded
if the safety relay and the contact extension are located in
the same electrical installation space.