10
Instruction Leaflet
IL29C203J
Installation Instructions for Motor Operator for
L-Frame and MDL-Frame Circuit Breakers and
Molded Case Switches
EATON C ORPORATION
www.eaton.com
Table 1-1 Available Motor Operator Ratings and Operating Conditions
Catalog Number
EOP4MT07 EOP4MT1 EOP4MT11A EOP4MT1 EOP4MT2 EOP4MT21
Style Number
Read Voltage (V)
120 AC
208 AC
240 AC
480 AC
125 DC
24 DC
Frequency (Hz)
50/60
50/60
50/60
50/60
DC
DC
Motor-in-Rush
Operator is an intermittent duty device. The safe duty cycle (OFF to ON to OFF) should not exceed one per minute.
Electrical Operating times at rated voltage.
a. To turn breaker ON - 0.2 second (12 cycles) max.
b. To turn breaker OFF - 0.2 second (12 cycles) max.
Motor Operating temperature; Class “A” temperature limits apply.
Applied Voltage should be no less than 85% or no more than 110% of rated voltage.
Operator application on supply of Vac utilizes a 480/115 Vac transformer. (Customer Supplied)
21
14
12
N/A
21
50
1483D43G17
1483D43G18
1483D43G19
1483D43G20
1483D43G21
1483D43G22