81O/U, 81R, 78V - Frequency Protection
Available elements:
81[1] ,81[2] ,81[3] ,81[4] ,81[5] ,81[6]
All frequency protective elements are identically structured.
Frequency - Measuring Principle
The frequency is calculated as the average of the measured values of the three
phase frequencies. Only valid measured frequency values are taken into
account. If a phase voltage is no longer measurable, this phase will be
excluded from the calculation of the average value.
The measuring principle of the frequency supervision is based in general on the time measurement of complete cycles,
whereby a new measurement is started at each zero passage. The influence of harmonics on the measuring result is
thus minimized.
Frequency tripping is sometimes not desired by low measured voltages which, for instance. occur during alternator
acceleration. All frequency supervision functions are blocked if the voltage is lower 0.15 times Vn.
www.eaton.com
681
V(t)
t
T
T
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...