EMR-4000
IM02602009E
Protection Elements Accuracy
The tripping delay relates to the time between alarm and trip.
The accuracy of the operating time relates to the time between fault entry
and the time when the protection element is picked-up.
Reference conditions for all Protection Elements: sine wave, at rated frequency, total harmonic distortion < 1%
Measuring criterion: Fundamental
Overcurrent Protection Elements:
50P[x]
Accuracy
Pickup
±1.5% of the setting value or 1% In.
Dropout Ratio
97% or 0.5% In
t
DEFT
±1% or ±10 ms
Operating Time
At testing current >= 2 times pickup value
<36ms
Disengaging Time
<55 ms
Overcurrent Protection Elements:
51P[x]
Accuracy
Pickup
±1.5% of the setting value or 1% In.
Dropout Ratio
97% or 0.5% x In
Operating Time
At testing current >= 2 times pickup value
<36 ms
Disengaging Time
<55 ms
t-Multiplier
±5% (according to selected curve)
Reset Mode
±5% (according to selected curve)
t-reset (Reset Mode = t-delay)
±1% or ±10 ms
Ground Current Elements:
50X[x] / 50R[x]
Accuracy
*3)
Pickup (measured ground current)
Pickup (calculated ground current)
±1.5% of the setting value or 1% In
±2.0% of the setting value or 1.5% In
Dropout Ratio
97% or 0.5% In
t
DEFT
±1% or ±10 ms
Operating Time
Starting from IE higher than 1.2 x IE>
<45 ms
Disengaging Time
<55 ms
t-reset (Reset Mode = t-delay)
±1% or ±10 ms
Ground Current Elements:
51X[x] / 51R[x]
Accuracy
*3)
Pickup (measured ground current)
Pickup (calculated ground current)
±1.5% of the setting value or 1% In
±2.0% of the setting value or 1.5% In
Dropout Ratio
97% or 0.5% In
Operating Time
Starting from IE higher than 1.1 x IE>
<45 ms
Disengaging Time
<55 ms
t-Multiplier
±5% (according to selected curve)
Reset Mode
±5% (according to selected curve)
t-reset (Reset Mode = t-delay)
±1% or ±10 ms
www.eaton.com
849
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...