LOP - Loss of Potential
Available elements:
LOP
Ensure that the LOP has enough time to block faulty tripping of modules that use LOP.
That means, the delay time of the LOP should to be shorter than the tripping delay of
modules that use LOP.
In case of transformer protection relays the LOP element uses current and
voltage measured at the winding side determined by paramter:
[System Para / VT / VT Winding Side ].
LOP function detects the loss of voltage in any of the voltage input measuring circuits and uses the following measured
values and information to detect an LOP condition:
•
Three-phase voltages;
•
Ratio of negative-to-positive sequence voltages;
•
Zero sequence voltage;
•
Three-phase currents;
•
Residual current (I0);
Once an LOP condition is detected and it lasts longer than an adjustable minimum pickup time, the LOP Pickup will be
set. The LOP Block will only be set if the LOP-Block control setting is set to enabled (activated). The LOP Pickup and
LOP Block signals can both be used as logical signal to block the protective functions which use the voltage information
such as voltage restraint. The minimum pickup timer is used to prevent short time incorrect operation of the LOP
function during breaker switching-on operation.
www.eaton.com
770
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...