RI-F100-C
OP532-EMC3P
-P2C1-V01-EA
TON
PRODUCT PROFILE
96mm x 96mm
SPECIFICATIONS
I
IP rating
: IP54 Front only (When fitted with rubber gasket)
Pulse Duration : Selectable 50...300mS
The meter is intended to be installed in Mechanical Environment `M1`,with
Shock and Vibrations of low significance, as per 2004/22/EC Directive.
The meter is intended to be installed in Electromagnetic Environment `E2`,
as per 2004/22/EC Directive.
- Communication in progress
LCD Indications
:
- Integration of energy
PT Primary
: 100V...600V (Programmable for any value)
Temperature
: Operating
: -10
°
C...55
°
C
Display
: Liquid crystal display with backlight 4 lines,
Display Update Time : 1 second for all parameters
- Maximum & Minimum Demand of Power
Auxiliary
: 85...270V AC, 47...63Hz
Installation Category : III (300V L-N)
Weight
: 318gms
Current indication as percentage of CT rating
PRG
- Unit is in configuration menu
Meter Type
: Indoor
Wiring Input
: 3 Ø
-
4 wire, 1 Ø
-
2 wire - P1, 3 Ø
- 3
wire
4 digits per line to show electrical Parameters
CT Primary
: 1/5A...6,000A (Programmable for any Value)
Humidity
: 85% non-condensing
Mounting
: Panel mounting
Display Scrolling
: Automatic / Manual
Pulse Resolution: Selectable 0.01...99.99kWh
PT Secondary
: 173...415V AC (L-L) (Programmable for any value)
CT Secondary
: 1 or 5A (x1.2)
Rated Input Voltage
: 3x230/400V
5th line, 8 digits to show energy Bar graph for
Frequency Range
: 47...63Hz (MID approved for 50Hz)
Storage
: -20
°
C...75
°
C
Pulse Output
: External 5...27VDC max./100mA max.
Communications
: RS485 Modbus RTU
WIRING GUIDELINES
equipment prior to undertaking any work. Always confirm absence of
supply prior to starting work using appropriate voltage detection
2. Wiring shall be done strictly according to the terminal layout. Confirm that
all connections are correct before energizing the equipment.
3. To reduce electromagnetic interference use of wires with adequate
ratings and twists of equal size are recommended. All connection should be
1. To prevent the risk of electrocution, always isolate the power supply to the
kept as short as possible.
4. Routing of connecting cables shall be away from any internal EMI source.
5.All cables used for connections must have a cross section
6. Copper cable should be used. (stranded or solid core cable)
7. All wiring to be in accordance with applicable local standards.
2
2
0
of 0.5mm to 2.5mm . (20 to14AWG ; 75 C (min) )
equipment.
SAFETY PRECAUTIONS
RESOLUTION
PT Ratio x CT Ratio
kWh
SERIAL COMMUNICATION
Interface standard and protocol
Communication address
Transmission Mode
Data types
Transmission distance
Transmission speed
Parity
Stop bits
RS485 AND MODBUS RTU
1...255
Half duplex
Float, Hex and Integer
500 Meter maximum
300, 600,1200, 2400, 4800, 9600,
19200 (in bps)
None, Odd, Even
1 or 2
ACCURACY
Accuracy
Measurement
Frequency
For L-N > 20V,
For L-L > 35V
Measurement
Accuracy
Voltage V
L-N
Voltage V
L-L
Current
±
0.5% of F.S.
±
0.5% of F.S.
±
0.5% of F.S.
±
0.1% of F.S.
100 ms
(max and independent of baud rate)
Response time
EN50470-3: CI.B
EN62053-23: CI.2
Active Power
Apparent power
Reactive Power
1%
1%
1%
Power factor
Active energy
Reactive energy
Apparent energy
MAX/MIN
Active Power
MAX/MIN
Reactive Power
MAX Apparent Power
±
0.01 (Digit)
1%
Class 1
1%
1%
PT Primary
Factory default
NOTE:
Once Programming Mode Is entered The parameters
below will be locked out after 15 Minutes. No further
CT Secondary
Pulse Duration
Network Selection
PT secondary
Energy Reset
CT Primary
Pulse width
adjustment is possible without returning to supplier.
CONFIGURATION LOCK PARAMETER DESCRIPTION
Doc. name : OP INST EMC3P-P2C1 OP532-EMC3P-P2C1-V01-EATON (Page 1 of 6)
Product
Outputs
Certification
MID
EMC3P-P2C1
Rs485 (Modbus RTU) & Pulse
(F.S - Full Scale)
I
TO COMPLY WITH MID CERTIFICATION
THE CT RATIO MUST BE SET BEFORE
PUTTING THE METER INTO SERVICE
NOTE :
EMC3P-P2C1
0.01K
0.1K
<15
<150
Note:
blinks every 5 sec. This indicates energy is being consumed.
ORDER INFORMATION
CAUTION
1. Read complete instructions prior to installation or operation of the unit.
2. Risk of electric shock. Only to be installed by competent personnel.
3. The equipment in its installed state must not come in close proximity to any
heating sources, oils, steam, caustic vapors or other unwanted process
by-products.
Safety related notifications, symbols and instructions that appear in this
operating manual or on the equipment must be strictly followed to ensure the
safety of personnel as well as the instrument.
No repairs, maintenance or adjustments are possible.
If the equipment is not used in a manner specified by the manufacturer it may
impair the protection provided by the equipment.
Do not use the equipment if there is any mechanical damage.
Ensure that the equipment is supplied with correct voltage.
Press
I
key for 3 sec. to check the current connection. If current connection
reverse meter will show in which phase connection is reversed.
0 - No any phase
2 - 2nd phase
1 - 1st phase
3 - 3rd phase
CURRENT CONNECTION INDICATION
Press PF key for 10 sec, displays CRC in first two row, HW & SW version no
in 3rd and 4th raw & serial no in last row.
DEVICE IDENTIFICATION
In automatic mode when any key is pressed, unit temporarily switches to
manual mode and the appropriate page is displayed, also if no key is
pressed for 5 sec, unit resumes automatic mode.
Press E ( ) button for 3 seconds to toggle between Automatic
and Manual
mode.
Note
:
By default unit operates in automatic mode.
In automatic mode online pages scroll automatically at the rate of 5
seconds per page. All the time, total import active energy will be displays &
at any other page of energy if no key is pressed for 1 min.
AUTOMATIC / MANUAL PAGE SCROLLING
1K
0.01M
0.1M
<1500
<15000
>15000