IL05003003E.pdf
ELC-AN06AANN
EXPLANATION
#25 H
40E1 O
R/W
To adj. GAIN
value of CH2
Voltage input: setting range is K-800 ~K4,000
Current input: setting range is K-800 ~K2,600
#26 H
40E2 O
R/W
To adj. GAIN
value of CH3
#27 H
40E3 O
R/W
To adj. GAIN
value of CH4
#28 H
40E4 O
R/W
To adj. GAIN
value of CH5
GAIN setting of CH5~CH6. Factory setting is K2,000 and unit is LSB.
The setting range is K-1,600~K8,000
#29 H
40E5 O
R/W
To adj. GAIN
value of CH6
#30
H 40E6
X
R
Error status
Data register stores the error status, refer to fault code chart for details.
#31 H
40E7 O
R/W
Communication
address setting
RS-485 communication address.
Setting range is K1~K255 and factory setting is K1
#32 H
40E8 O
R/W
Communication
baud rate setting
Communication baud rate (4,800, 9,600, 19,200, 38,400, 57,600 and 115,200 bps).
For ASCII mode, date format is 7Bits, even, 1 stop bit (7,E,1). For RTU mode, date
format is 8Bits, even, 1 stop bit (8, E,1).
b0: 4,800 bps (bit/sec), b1: 9,600 bps (bit/sec). (factory setting)
b2: 19,200 bps (bit/sec), b3: 38,400 bps (bit/sec).
b4: 57,600 bps (bit/sec), b5: 115,200 bps (bit/sec).
b6~b13: Reserved, b14: switch between low bit and high bit of CRC code (only for
RTU mode), b15: RTU mode.
#33 H
40E9 O
R/W
Reset to factory
setting and set
characteristics
adjustable
priority
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH6 CH5 CH4
CH3
CH2
CH1
Example: Setting of CH1
1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#18, CR#24).
When b0=1, inhibit user to adjust OFFSET and GAIN value of CH1.
2. b1 means if characteristic register is latched. b1=0 (factory setting, latched),
b1=1 (not latched).
3. b2: Set to 1 and ELC-AN06AANN will be reset to factory settings.
The setting of CH5~CH6, give CH5 setting for example: b13, b12:
00: can be adjusted, latched, 01: can be adjusted, non-latched.
10: inhibit adjust, 11: reset to factory settings and clear b12, b13 to 0.
#34
H 40EA
O
R
System Version
Display software version in hexadecimal. Example: H 010A = version 1.0A.
#35~#48
System used
O means latched. X means non-latched.
R means can read data by using FROM command or RS-485. W means can write data by using TO command or RS-485.
LSB (Least Significant Bit): 1. Voltage input: 1
LSB
=10V/2,000=5mV. 2. Current input: 1
LSB
=20mA/1,000=20
μ
A.
3. Voltage output: 1
LSB
=10V/4,000=2.5mV. 4. Current output: 1
LSB
=20mA/4,000=5
μ
A.
Explanation:
1. CR#0: The ELC model type.
2. CR#1: b11~b0 is used to set 4 inner channels working mode of analog input module (AD).
b12~b15 is used to set 2 channels working mode of analog output module (DA). Every channel
has four modes to set and can be set individually. For example: if setting CH1 to mode 0
(b2~b0=000), CH2 to mode 1(b5~b3=001), CH3: mode2 (b8~b6=010), CH4: mode
3(b11~b9=011). It needs to set b0~b11 to H688. If setting CH5: mode 2 (b13~b12=10), CH6:
mode 1 (b15~b14=01), it needs to set b12~b15 to H5. The factory setting is H0000.
3. CR#2 ~ CR#5: Used to set the number of input readings used for the average temperature
calculation. The available range is K1~K100 and factory setting is K10.
4. CR#6 to CR#9: they are used to save the average value of input signal of CH1~CH4.
5. CR#10 ~ CR#11 are used to set the output value of CH5 and CH6. The setting range is
K0~K4,000. The factory setting is K0 and unit is LSB.
6. CR#12 ~ CR#15: they are used to save the present value of input signal of CH1~CH4.
7. CR#16, CR#17, CR#28, CR#29 are reserved.
8. CR #18~ CR #21: the content is the value of adjusting OFFSET value of CH1~CH4 if analog
input voltage or current is 0 after it transfers from analog to digital. Voltage setting range:
-5V~+5V(-1,000
LSB
~+1,000
LSB
). Current setting range: -20mA~+20mA (-1,000
LSB
~+1,000
LSB
).
9. CR #22~ CR #23: the content is the value of adjusting OFFSET value of CH5~CH6 if analog
input voltage or current is 0 after it transfers from analog to digital. The factory setting is K0 and
the unit is LSB. The setting range is -2,000~+2,000. Voltage setting range:
-5V~+5V(-2,000
LSB
~+2,000
LSB
). Current setting range: -10mA~+10mA (-2,000
LSB
~+2,000
LSB
).
10. CR #24~ CR #27: That is the value of adjust GAIN value of CH1~CH4. That is the value of
analog input voltage or current when conversion value from analog signal to digital is 4,000.
Voltage setting range: -4V~+20V(-800
LSB
~+4,000
LSB
). Current setting range: -16mA~+52mA
(-800
LSB
~+2,600
LSB
). But it needs to notice that GAIN VALUE – OFFSET VALUE =
+200
LSB
~+3,000
LSB
(voltage) or +200
LSB
~+1,600
LSB
(current). When this value under this range,
the resolution of the input signal will be thin and the variation of value will be larger. When this
value exceeds this range, the resolution of input signal will be thick and the variation of value
will be smaller.
11. CR #28~ CR #29: That is the value of adjust GAIN value of CH5~CH6. That is the value of
analog input voltage or current when conversion value from analog signal to digital is 2,000.
Voltage setting range: -4V~+20V(-1,600
LSB
~+8,000
LSB
). Current setting range: -8 mA ~+40 mA
(-1,600
LSB
~+8,000
LSB
). But it needs to notice that GAIN VALUE – OFFSET VALUE = +400
LSB
~+6,000
LSB
(voltage/current). When this value under this range, the resolution of the input signal
will be thin and the variation of value will be larger. When this value exceeds this range, the
resolution of input signal will be thick and the variation of value will be smaller.
12. CR#30 is fault code. Please refer to the following chart.
Fault description
Content
b15~b8
b7
b6
b5
b4
b3
b2
b1
b0
Power source abnormal
(Low voltage alarm)
K1(H1)
Reserved
0 0 0 0 0 0 0 1
User setting D/A output
exceeds range
K2(H2)
0 0 0 0 0 0 1 0
Setting mode error
K4(H4)
0 0 0 0 0 1 0 0
Offset/Gain error
K8(H8)
0 0 0 0 1 0 0 0
Hardware malfunction
K16(H10)
0 0 0 1 0 0 0 0
Digital range error
K32(H20)
0 0 1 0 0 0 0 0
Average times setting error
K64(H40)
0 1 0 0 0 0 0 0
Command error
K128(H80)
1 0 0 0 0 0 0 0
Note:
Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the same
time. 0 means normal and 1 means having fault.
13. CR#31: RS-485 communication address. Setting range is 01~255 and factory setting is K1.
14. CR#32: RS-485 communication baud rate: 4,800, 9,600, 19,200, 38,400, 57,600 and 115,200.
b0:4,800bps, b1:9,600bps (factory setting), b2:19,200bps, b3:38,400 bps, b4:57,600 bps,
b5:115,200 bps, b6~b13: Reserved, b14: switch between low bit and high bit of CRC code (only
for RTU mode) b15: ASCII / RTU mode. For ASCII mode, date format is 7Bits, even, 1 stop bit
(7,E,1). For RTU mode, date format is 8Bits, even, 1 stop bit (8,E,1).
15. CR#33 is used to set the inner function priority. For example: characteristic register. Output
latched function will save output setting in the inner memory before loss power.
16. The corresponding parameters address H 40C8~H 40EA of CR#0~CR#34 can provide user to
read/write data by RS-485.
a) Communication baud rate: 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps.
b) Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7,E,1). Communication
format of RTU mode is 8Bit, even bit, 1 stop bit (8,E,1).
c) Function code: 03H—read data from register. 06H—write a WORD into register.
10H—write many WORDs into register.
4
ADJUST A/D CONVERSION CHARACTERISTIC CURVE
4.1 Adjust A/D Conversion Characteristic Curve of CH1~CH4
Voltage input mode
+2000
+1000
-1000
10V
digital output
Voltage
input
-2000
-6V
-10V
6V
5V
2V
0
Mod e 1
Mod e 0
GAIN
OFFSET
Mode 0 of CR#1:
GAIN=5V(1,000
LSB
), OFFSET=0V (0
LSB
).
Mode 1 of CR#1:
GAIN=6V(1,200
LSB
), OFFSET=2V (400
LSB
).
GAIN:
Voltage input value when digital output is 1,000.
Setting range is -4V~+20V(-800
LSB
~ +4,000
LSB
)
OFFSET:
Voltage input value when digital output is 0.
Setting range: -5V~+5V(-1,000
LSB
~ +1,000
LSB
)
GAIN
-
OFFSET:
Setting range is +1V~+15V (+200
LSB
~ +3,000
LSB
)
Current input mode:
+1000
Digital output
Current
Input
-1000
-12mA
-20mA
4mA
0
Mod e 2
Mod e 3
OFFSET
20mA
GAIN
Mode 2 of CR#1:
GAIN = 20mA(1,000
LSB
), OFFSET=4mA (200
LSB
).
Mode 3 of CR#1: GAIN = 20mA(1,000
LSB
), OFFSET=0mA (0
LSB
).
GAIN:
Current input value when digital output is +1,000.
Setting range is -16 mA ~+52 mA (-800
LSB
~
+2,600
LSB
)
OFFSET:
Current input value when digital output value is 0.
Setting range is -20 mA~+20 mA (-1,000
LSB
~
+1,000
LSB
)
GAIN
-
OFFSET: Setting range is +4mA ~ +32mA (200
LSB
~ +1,600
LSB
)
The chart above is to adjust A/D conversion characteristic curve of voltage input mode and current
input mode. Users can adjust conversion characteristic curve by changing OFFSET values
(CR#18~CR#21) and GAIN values (CR#24~CR#27) depend on application.
Voltage input: 1
LSB
=10V/2,000=5mV. Current input 1
LSB
=20mA/1,000= 20
μ
A.
4.2 Adjust D/A Conversion Characteristic Curve of CH5~CH6
Voltage output mode
0
+2000
+4000
2V
5V
6V
10V
OFFSET
GAIN
Voltage output
mode 1
mode 0
Digital
input
Mode 0 of CR#1:
GAIN = 5V(2,000
LSB
), OFFSET=0V (0
LSB
)
Mode 1 of CR#1:
GAIN = 6V(2,400
LSB
), OFFSET=2V (800
LSB
).
GAIN:
Voltage output value when digital input is K2,000.
Setting range is -4V~+20V(-1,600
LSB
~+8,000
LSB
).
OFFSET:
Voltage output value when digital input is K0.
Setting range: -5V~+5V(-2,000
LSB
~ +2,000
LSB
).
GAIN
-
OFFSET: Setting range is +1V~+15V(+400
LSB
~ +6,000
LSB
)
Current output mode:
0
+2000
+4000
20mA
OFFSET
GAIN
12mA
10mA
4mA
Current output
Mode 2
Mode 3
Digital
input
Mode 2 of CR#1: GAIN = 12mA(2,400
LSB
),OFFSET=4mA (800
LSB
).
Mode 3 of CR#1: GAIN = 10mA(2,000
LSB
), OFFSET=0mA (0
LSB
).
GAIN:
Current output value when digital input value is
K2,000. Setting range is -8 mA ~ +40 mA (-1,600
LSB
~+8,000
LSB
).
OFFSET:
Current output value when digital input is K0. Setting
range is -10 mA ~ +10 mA (-2,000
LSB
~+2,000
LSB
).
GAIN
-
OFFSET: Setting range is +2mA~+30mA(+400
LSB
~+6,000
LSB
)
The chart above is to adjust D/A conversion characteristic curve of voltage output mode and current
output mode. Users can adjust conversion characteristic curve by changing OFFSET values
(CR#14~CR#15) and GAIN values (CR#18~CR#19) depend on application.
Voltage output: 1
LSB
=10V/4,000=2.5mV., Current output: 1
LSB
=20mA/4,000=5
μ
A.
5
INSTALLATION & WIRING
1.
Installation of the DIN rail
The ELC can be secured to a cabinet by using the DIN rail that is 35mm high with a depth of 7.5mm.
When mounting the ELC on the DIN rail, be sure to use the end bracket to stop any side-to-side
motion of the ELC, thus to reduce the chance of the wires being pulled loose. At the bottom of the
ELC is a small retaining clip. To secure the ELC to the DIN rail, place it onto the rail and gently push
up the clip.
To remove it, pull down the retaining clip and gently pull the
ELC away from the DIN rail. As shown on the right:
When installing the ELC, make sure that it is installed in an
enclosure with sufficient space (as shown on the right) to its
surroundings so as to allow heat dissipation.
D
D
D
D
E
L
C
D>50mm
2. Wiring
22-16AWG
<1.5mm
Notes:
1. Please use 22-16AWG (1.5mm) wiring (either single or multiple
core) for I/O wiring terminals. The specification for the terminals is
as shown on the left. ELC terminal screws should be tightened to
1.95 kg-cm (1.7 lb-in). Use Copper Conductor Only, 60/75 °C.
2. I/O signal wires or power supply should not run through the same
multi-wire cable or conduit.
6
INITIAL ELC START-UP
Lamp display:
1.
Upon power-up, the ERROR LED will light for 0.5 seconds the POWER LED will light
continuously.
2.
No errors= POWER LED on and ERROR LED off.
Low Voltage error (lower than 19.5V), ERROR LED will blink continuously till the power
supply rises above 19.5V.
3.
ELC-AN06AANN connected to ELC in series = RUN LED on MPU will be lit and A/D