manualshive.com logo in svg
background image

IL05003022E.pdf 

 

2

Compact Installation reference: 

See Fig. 3a in lower left, when ELC-485APTR is separated from mounting plate, it can be used as the last extension module 
with its RS-485 port connecting to ELC controller’s (see Fig. 3b for illustration). This connection is feasible for ELC controller to 
connect AC Motor Drive within 5 meters. 

 

 

MVX 9000

EL

C

-EX0

8N

N

D

N

RS

-2

32

RS

-4

85

x16

EL

C

-PC

12

N

N

D

R

0

1

STOP

0

1

RUN

x16

E

LC-

CO

PB

DP

 

Fig. 3a 

Fig. 3b 

 

PIN Explanation of COM1, COM2, and RJ12 

COM1-DB9 female 

PIN Definition 

RJ12 of AC Motor Drive side 

PIN Definition 

1 RS485- 

+15V 

2 RS485+ 

GND 

3 RS485+ 

SG- 

4 RS485- 

SG+ 

1

2

3

4

5

6

7

8

9

 

5~9 NC 

 

5, 6 

Reserved 

 

COM2-DB9 male 

PIN Definition 

RJ12 of ELC-485APTR side 

PIN Definition 

3, 6 

RS485- 

RS-485+ 

8 RS485+ 

RS-485- 

5, 9 

GND 

GND 

5

2

1

4

3

6

7

8

9

 

1, 2, 4, 7 

NC 

 

1, 2, 6 

NC 

 

4   

ELC-485APTR Termination Resistor Application 

In all RS-485 installations, the cable must be correctly terminated with two sets of resistors, one set at each end of the network 
(4,000 feet maximum total cable length). This applies even if you are only using one slave node connected to one master 
device. The terminating resistors prevent reflection problems that can interfere with data transmission. The resistance value of 
the terminating resistors should match the characteristic impedance of the cable. A typical value is 120 ohms. The terminating 
resistors must be placed at the two farthest ends of the RS-485 network, regardless of where the master device is. In some 
cases master device RS-485 ports have built in or optional terminating resistors. Beware of your network (whether it has one 
node or 32 nodes) having only two sets of terminating resistors. 

ELC-485APTR’s Termination Resistor Switch is located inside of the 
adapter’s extension port. 

Switch ON the termination resistor for ELC-485APTR on the both ends only 
and switch OFF (factory setting) for the modules between both ends when 
modules are connecting in parallel.

 

Termination Resistor Switch

Fig. 4

 

 