4. Inspection and Field  Testing

Series G molded case circuit breakers are designed to provide years 

of almost maintenance-free operation. The following procedure 

describes how to inspect and test a circuit breaker in service.

Inspection

Circuit breakers in service should be inspected periodically. The 

inspection should include the following checks (4-1 through 4-7):

 WARNING

BEFORE INSPECTING THE CIRCUIT BREAKER  IN AN ELECTRICAL SYSTEM, 

MAKE SURE THE CIRCUIT BREAKER  IS SWITCHED TO THE OFF POSITION 

AND THAT THERE IS NO VOLTAGE PRESE NT WHERE WORK IS TO BE 

PERFORMED. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED 

APPLICATIONS TO ENSURE VOLTAGE IS PRESE NT. THE VOLTAGES IN 

ENERGIZED EQUIPMENT CAN CAUSE DEATH OR SEVERE PERSONAL 

INJ URY.

 CAUTION

MAKE SURE THAT CLEANING AGENTS OR SOLVENTS USED TO CLEAN 

THE CIRCUIT BREAKER  ARE SUITABLE FOR THE J OB. SOME COMMERCIAL 

CLEANING AGENTS WILL DAMAGE THE NAME PLATES OR MOLDED 

PARTS.

4-1. Remove dust, dirt, soot, grease, or moisture from the surface 

of the circuit breaker using a lint-free dry cloth, brush, or vacuum 

cleaner. Do not blow debris into circuit breaker. If contamination is 

found, look for the source and eliminate the problem.
4-2. Switch circuit breaker to ON and OFF several times to be sure 

that the mechanical linkages are free and do not bind. If mechanical 

linkages are not free, replace circuit breaker. 
4-3. With the circuit breaker in the ON position, press the PUSH 

TO-TRIP button to mechanically trip the circuit breaker. Trip, reset, 

and switch circuit breaker ON several times. If mechanism does 

not reset each time the circuit breaker is tripped, replace the circuit 

breaker. 
4-4. Check base, cover, and operating handle for cracks, chipping, 

and discoloration. Circuit breakers should be replaced if cracks or 

severe discoloration is found.
4-5. Check terminals and connectors for looseness or signs of over-

heating. Overheating will show as discoloration, melting, or blister-

ing of conductor insulation, or as pitting or melting of conductor sur-

faces due to arcing. If there is no evidence of overheating or loose-

ness, do not disturb or tighten the connections. If there is evidence 

of overheating,terminations should be cleaned or replaced. Before 

reenergizing the circuit breaker, all terminations and cable should be 

refurbished to the condition when originally installed. 
4-6. Check circuit breaker mounting hardware, tighten if necessary.
4-7. Check area where circuit breaker is installed for any safety haz-

types of chemicals can cause deterioration of electrical connections. 

Field Testing

NEMA Standards.

Содержание EG-DC Series

Страница 1: ...EG DC Circuit Breaker and Molded Case Switch H02 Effective June 2011 E125H DC 68C 3719 H03 Industrial Circuit Breaker E125H DC Interrupting Capacity PUSH TO TRIP NEMA Ratings kA 42 50 65 Poles In Seri...

Страница 2: ...T WHILE IT IS ENERGIZED DEATH SEVERE PERSONAL INJURY OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE...

Страница 3: ...breaker and as applicable installing accessories interphase barriers and terminals mounting the circuit breaker connecting the line and load conductors torquing terminals and attaching terminal shiel...

Страница 4: ...D HARDWARE WHEN SPECIAL HARDWARE IS NEEDED FOR EXAMPLE WITH THE ELECTRICAL OPERATOR THE INSTRUCTION LEAFLET DESCRIBI NG THE ACCESSORY ALSO DESCRIBES THE SPECIAL MOU NTING ARRANGEMENTS 2 6 To mount the...

Страница 5: ...he circuit breaker handles and the PUSH TO TRIP button in the trip unit The circuit breaker handle has three positions two of which are shown on the cover with raised lettering to indicate ON and OFF...

Страница 6: ...ntamination is found look for the source and eliminate the problem 4 2 Switch circuit breaker to ON and OFF several times to be sure that the mechanical linkages are free and do not bind If mechanical...

Страница 7: ...7 Instruction Leaflet IL01202013EH01 Installation Instructions For EG DC Circuit Breaker and Molded Case Switch EATON CORPORATION www eaton com Notes Effective June 2011...

Страница 8: ...s required you should consult an authorized Eaton sales representative The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling pol...

Отзывы: