manualshive.com logo in svg
background image

Control Devices EFS, EFD and EDS Series

Installation & Maintenance Information

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 899

APPLICATION

EFS and EDS Series Control Devices are used in conjunction with magnetic starters or contactors for 

remote control of motors and to visually indicate that the desired function is being performed.  EFD Se-

ries Manual Motor Starting Switch Enclosures are used for manually starting or stopping small AC or DC 

motors.  EFD Series Circuit Breakers provide overload protection to the load side conductors.
EFS/EDS (dead end) and EFSC/EDSC (through feed) Series Pushbutton Stations, Selector Switches and 

Factory Sealed Pilot Lights are used separately or in combination with a variety of standard features and 

special options available.
EFS Series Control Devices are suitable for use in Class I, Groups B, C, D (Division 1), Class II, Groups E, 

F, G, and Class Ill hazardous (classified) locations, as defined by the National Electrical Code

®

 (NEC) and 

Canadian Electrical Code (CEC).  EDS and EFD Series Control Devices are suitable for  

Class I, Group B (Division 1) usage when they are identified by the suffix GB added to the catalog number 

with seals immediately adjacent to each conduit opening.  

DSD Series Control Device Covers are suitable for Class I, 

Groups B (Division 2 only), C, D and Class II, Groups E, F, 

G as standard.
The XT suffix provides an expanded temperature range 

of -50°C to +60°C for EDS and EFS Assemblies, DSD 

and DS Covers and FlexStation™ Components. For iron 

assemblies, only EDS iron back boxes externally marked 

with an “X” on the conduit hub can be assembled with XT 

suffix iron covers. All aluminum back boxes (no marking) 

may be assembled with XT suffix aluminum covers. XT 

suffix covers can only be used with single gang back boxes and cannot be used with the GB suffix. The 

conduit sealing requirements are displayed in Conduit Seal Requirements Chart.

INSTALLATION

1. 

Select a mounting location that will provide suitable strength and rigidity for supporting all 

contained wiring and control devices.  Figure 2 shows the mounting dimensions of all EFS, EFD 

and EDS Device Bodies.  Drill and tap mounting holes for 5/16 - 18 bolts.

2. 

Securely fasten the device body to the mounting surface, then attach the body into the conduit 

system.

3. 

Pull supply wires into the enclosure, making them just long enough to make the required 

connections.

4. 

Make the electrical connections utilizing the wiring scheme established for your system.  See 

Figures 1A and 1B for the contact diagrams of EFS and EDS Pushbutton Stations and Selector 

Switches.

Figure 1A

Figure 1B

PILOT LIGHTS

Figure 1C

The field wiring terminals on the switch units used for pushbutton or selector switch stations are marked.  

The       and “0” indicate normally open contacts; and       and “C” indicate normally closed contacts of 

the switch.  These switches are provided with binding screw terminals.  For EDS/EDSC Series Toggle 

Switches: splice factory sealed wires to supply wires using suitable connectors.

• 

Strip the insulation on each conductor wire back 3/8”.

• 

Use a slotted or Phillips head screwdriver to loosen the field wiring terminal screws the required 

three (3) or four (4) turns.

• 

Insert the bare wire conductor(s) on either side of the terminal screw(s), under the terminal wire 

clamp(s) and securely tighten the screw(s).

           

NOTE:

 Do not exceed 15 in.-lbs. of torque.

• 

Pilot lights and sealing wells are furnished with pigtail leads for field connection by use of wire 

nuts.

• 

For EFD Manual Motor Starters, install heaters as required.  Refer to manufacturer’s heater 

selector listings for each motor starting switch.  Mount the starter into enclosure and make 

electrical connections utilizing the wiring scheme established for the motor starting switch.

5. 

Test wiring for correctness with continuity checks and also for unwanted grounds with an insulation 

resistance tester.

6. 

Select the proper cover for assembly. Similar cover and back box materials can only be used (e.g. 

iron with iron; aluminum with aluminum). Assemble cover to the device body with the cover 

screws. Check the tightness of the cover screws to ensure that the cover assembly is securely 

fastened.

7. 

Pour Chico

®

 Sealing Compound into EYS/EYD Series Sealing Fittings (where used) in accordance 

with the instructions with each sealing fitting used.

NOTE: 

Seals are not required for Class I, Division 2.

PILOT LAMP REPLACEMENT

110-125 Volt Circuit: 6 watt, T21/2 miniature bayonet base

LED Replacement: 24, 120 VAC, T31/4 miniature bayonet base

MAINTENANCE

1. 

Frequent inspection should be made.  A schedule for maintenance checks should be determined by 

the environment and frequency of use.  It is recommended that it should be at least once a year.

2. 

Perform  visual, electrical  and mechanical checks on all components on a regular basis. 
Visually check for undue heating evidenced by discoloration of wires or other components, 

damaged or worn parts or leakage evidenced by water or corrosion in the interior. 
Electrically check to make sure that all connections are clean and tight, and that contacts in the 

components make or break as required. 
Mechanically check that all parts are properly assembled, and that operating mechanisms move 

freely.

Figure 2

!

CAUTION

Hammers or prying tools must not be allowed to damage the flat ground joint surfaces.  Do not 

handle covers roughly or place them on surfaces that might damage or scratch the flat ground joint 

surfaces.

!

CAUTION

Hazardous location information indicating the class and group the product is approved for is marked 

on the nameplate of each device.  Conduit sealing fittings may be required to be installed to comply 

with the requirements of the latest edition of the CEC or NEC, Section 501-5 and/or 502-5, plus any 

other applicable standards.  Review nameplate for specific information.

!

WARNING

Electrical power must be OFF before and during installation and maintenance.

!

WARNING

No conduit openings are to be added in the field.  All unused conduit openings must be plugged 

and plugs must be a minimum of 1/8 inch thick and have a minimum of five (5) threads engagement 

(seven (7) threads for Group B applications).  For EFS Enclosures with 1 inch hub(s), EDS 3-pole Snap 

Switches and EFD/EDS with “GB” suffix, all conduits must be sealed within 18 in. of the enclosure.

!

WARNING

Check for dirt, grit or other foreign material on the mating surfaces of the cover and the device body.  

Be certain that each surface is wiped completely clean before assembling.  Surfaces must seat fully  

against each other to provide a proper explosionproof seal.

!

WARNING

Always disconnect primary power source before opening the enclosure for inspection or service.

All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with 

Eaton’s Crouse-Hinds Division’s “Terms and Conditions of Sale,” and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes 

all risk and liability whatsoever in connection therewith.

                               Eaton’s Crouse-Hinds Division                                                                                                                                    IF 899

                               1201 Wolf Street, Syracuse, NY 13208  •  U.S.A.                                                                                                  Revision 5

                               Copyright© 2016                                                                                                                                           Revised 06/16

                                                                                                                                                                                              Supercedes 06/00

Conduit Seal Requirements (Class I, Division 1)

Standard

XT Suffix

EDS

None

Within 1.5”

EDS GB Suffix

Within 1.5”

Not Allowed

EFS

Within 5 ft. on 1” conduit;         

none for 1/2” or 3/4” hub size

Within 18”

Отзывы: