Control commands for easy600
72
09/10 MN05013007Z-EN
Read/write function
blocks
Overview
The first data byte of the string to be written on
command
represents a command for easy600 and defines the meaning
of the remaining 6 data bytes. The following table shows the
possible commands.
Operands Meaning
Command
Page
A1 – A8
„Analog value comparator A1 – A8: write actual values
(function, comparison values)“
22
hex
– 29
hex
C1 – C8
„Counter relays C1 – C8: read actual value“
3B
hex
– 42
hex
„Counter relay C1 – C8: write reference value“
09
hex
– 10
hex
„Counter relay C1 – C8: read reference value“
43
hex
– 4A
hex
T1 – T8
„Timing relays T1 – T8: read actual value (timing range,
actual value, switching function)“
2B
hex
– 32
hex
„Timing relays T1 – T8: write parameters (timing range,
reference value, switching function)“
01
hex
– 08
hex
Ö
1 –
Ö
4
“Time switch
Ö
1 –
Ö
4: read actual value
(channel, ON time, OFF time)”
4B
hex
– 5A
hex
“Time switch
Ö
1 –
Ö
4: read setpoint value
(channel, ON time, OFF time)”
12
hex
– 21
hex
Содержание EASY222-DN
Страница 10: ...Contents 6 09 10 MN05013007Z EN...
Страница 34: ...30 09 10 MN05013007Z EN...
Страница 258: ...254 09 10 MN05013007Z EN...
Страница 274: ...Glossary 270 09 10 MN05013007Z EN...
Страница 284: ...Alphabetical index 09 10 MN05013007Z EN 280...