Safety notices
E02A INTEGRATED RACK TYPE AIR CONDITIONER
UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com
2. Safety notices
In order to use the equipment correctly, the following safety precautions should be strictly followed.
2.1 Transport
•
Keep the air conditioner in a horizontal state during transportation.
•
If the cabinet needs to be transported, please remove the air conditioner and pack it separately
before transportation.
2.2 Storage
•
Storage environment should not exceed 70°.
•
Keep the air conditioner in a horizontal state during storage.
2.3 Unpacking
•
Prior to and during unpacking, make a visual inspection of the air conditioner to see whether any damage has
occurred during transportation. Pay special attention to loose parts, dents, scratches and oil leakages.
•
Any damage must be reported immediately to the forwarder agent.
•
Before disposing of packing material ensure that it does not contain any loose components.
2.4 Installation
•
Select a site for the enclosure with good ventilation;
•
The location should be free from excessive dirt and moisture;
•
The ambient temperature does not 45˚C;
•
The enclosure is sealed on all sides (IP54). If the seal is not good, too much condensate may be generated;
•
Air inlet and outlet should not be blocked by obstacles inside the enclosure at the inside of the enclosure;
•
The duct size outside the air conditioner cabinet should not be less than the limit value in the following figure 2.
•
Units are only fitted horizontally in the specified position. The maximum inclination angle shall not be greater
than 2°;
•
Losses from the components installed in the enclosure must not exceed the specific refrigeration capacity of
the air conditioner itself;
•
The user must not modify the air conditioner in any way.
Figure 2
Distance Diagram