Installation instructions

Complete Tee Connector kit includes: 

1 –  Moulded tee connector

1 –  Clamping screw

1 –  Basic insulating plug

1 –  Rubber cap

1 –  Cable adapter

1 –  Bi-metallic conductor contact

   – Silicone lubricant

   – Paper towel

   – Installation instructions

Step 1

1.  Train the cable to the desired finished position. (See 

Figure 2.) Be sure that the cable is long enough to 

permit movement of the tee connector from the 

apparatus bushing to a standoff bushing.

2.  Initially, cut the cable 100 mm past the bushing 

centerline.

ote:

N

This is the initial length of the cable to ensure that 

the screen wires are long enough to reach the 

earthing eye on the tee connector. The cable will 

be cut to its final length in a later step.

3.  Remove 435 mm of the cable sheath. 
4.  Fold the screen wires back over the sheath and 

secure them with two wraps of vinyl tape. (This step 

is optional. The vinyl tape is not included in the kit.)

5.  Position the cable to its final position and cut it 50 

mm from the centerline of the apparatus bushing. 

See Figure 3. 

Figure 2.   

100 mm

VINYL TAPE

SCREEN WIRES

INSULATION SCREEN

435 mm

 WARNING 

Hazardous voltage. All associated apparatus must be 

de-energized during installation and/or maintenance. 

Failure to comply may result in death, severe personal 

injury and equipment damage.

2

DT400/436 tee connector installation instructions

   MN650001EN   September 2014   www.cooperpower.com

Содержание DT400

Страница 1: ...Lorem ipsum dolor sit Amat Connectors and Splices MN650001EN Effective September 2014 Supersedes IS550 30 1 March 2011 DT400 436 Tee Connector Installation Instructions...

Страница 2: ...TING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In no event...

Страница 3: ...DUCT INFORMATION Introduction 1 Acceptance and Initial Inspection 1 Handling and Storage 1 Standards 1 INSTALLATION PROCEDURE Installation Instructions 2 iii DT400 436 tee connector installation instr...

Страница 4: ...Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low vol...

Страница 5: ...rocedures or process described nor provide directions for meeting every possible contingency during installation operation or maintenance For additional information contact your representative Accepta...

Страница 6: ...re long enough to reach the earthing eye on the tee connector The cable will be cut to its final length in a later step 3 Remove 435 mm of the cable sheath 4 Fold the screen wires back over the sheath...

Страница 7: ...per face is parallel to the face of the bushing 3 Crimp the connector starting at the shoulder as shown Rotate the crimping tool 90 for each successive crimp 4 Remove any inhibitor that may come out o...

Страница 8: ...mm socket wrench Step 8 1 Clean and apply lubricant to the insulating plug and the tee connector interface 2 Insert the insulating plug into the connector and engage the threads of the clamping screw...

Страница 9: ...24 kV Figure 9 Installation of cap CAUTION The apparatus bushing and tee connector should not support the weight of the cable Clamp the cable immediately below the cable screen adapter Failure to com...

Страница 10: ...This page is intentionally left blank 6 DT400 436 tee connector installation instructions MN650001EN September 2014 www cooperpower com...

Страница 11: ...This page is intentionally left blank 7 DT400 436 tee connector installation instructions MN650001EN September 2014 www cooperpower com...

Страница 12: ...use these trademarks without the prior written consent of Eaton Eaton 1000 Eaton Boulevard Cleveland OH 44122 United States Eaton com Eaton s Cooper Power Systems Business 2300 Badger Drive Waukesha...

Отзывы: