4 Operation
4.4 Potentiometer settings
100
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
4.4.1.3 t-Stop
In the industry, the t-Stop stop ramp is used predominantly for applications
involving pumps, conveyor belts, and belt drives. For example, it can be used
to prevent goods being conveyed from toppling over (e.g., bottles on a
conveyor belt), V-belts from slipping, and water impact caused by valves
being closed from occurring.
With all other applications, the parameter t-Stop can also be set to zero in
order to prevent any unnecessary temperature rise in the motor.
A soft stop ramp has the same temperature characteristics as a start. It also
therefore causes the heating of the soft starter and motor, and must be
taken into account when determining the starting frequency. The stop ramp
terminates at a set value of U-Start. A correct setting will cause the minimum
torque to be generated at which the motor still turns. At lower voltages
(torques), the machine remains at standstill due to losses or friction.
The stop ramp is activated when the start command is turned off (low signal
on control signal teA1). The drive then moves with the set stop time
(t-Stop) to the value of the start voltage (U-Start). When this is reached, the
soft starter switches off the output. If the motor still is still turning, it will
perform an uncontrolled stop from this point. The soft stop time is default set
to 0 s, in other words the motor performs an uncontrolled stop.
Figure 72: Operation with
①
and without
②
soft stop
a
With stop ramp (+A1 = OFF, t-Stop > 0)
b
Without stop ramp (+A1 0 OFF, t-Stop = 0 s) or via control signal terminal EN
(in the case of sizes 3 and 4) or via SmartWire-DT with t-Stop = 0
+A1 (Start)
RUN
+A1 (Start)
RUN
n
Motor
U
out
U-Start
n
Motor
U
out
t-Stop
①
②
Содержание DS7 Series
Страница 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Страница 4: ...II...
Страница 14: ...0 About this Manual 0 8 Units of measurement 10 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 64: ...2 Engineering 2 15 Example of other load cycles 60 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 122: ...6 Parameterization 6 2 Default settings of the basic device 118 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 148: ...7 Connection examples 7 3 Size 3 and 4 41 200 A 144 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...