DEV20 Sounder Technical Manual

DEV20 SOUNDER TECHNICAL MANUAL

  

TMF0047.A

  www.eaton.com

Mounting Kit

A due grounding and assembly of the device according to EN 60728-11/ VDE 0855-1 has 

to be observed.
The device shall only be installed on plain, stable and vibration-free surfaces.
If vibrations may occur, additionally the pictured assembling kit has to be used.

Art .-Nr . /Art no .

Montage-Set  

21591099

S0/S1 sound Signal choice table

0

Continuous 440 Hz

1

Continuous 554 Hz

2

Continuous 660 Hz

3

Continuous 800 Hz

4

Continuous 1000 Hz

5

Continuous 2400 Hz

6

Intermittent 420 Hz 0,800 Hz

(0,625 s on | 0,625 s off)

7

Intermittent 554 Hz @ 0,875 Hz

(0,571 s on | 0,571 s off)

8

Intermittent 660 Hz @ 3,333 Hz

(0,150 s on | 0,150 s off)

9

Intermittent 660 Hz @ 0,278 Hz

(1,800 s on | 1,800 s off)

10

Intermittent 800 Hz ® 0,800 Hz

(0,250 s on | 1,000 s off)

11

Intermittent 800 Hz @ 2,000 Hz

(0,250 s on | 0,250 s off)

12

Intermittent 1000 Hz @ 0,500 Hz

(1,000 s on | 1,000 s off)

13

Intermittent 1000 Hz 1,000 Hz

(0,500 s on | 0,500 s off)

14

Intermittent 2400 Hz 1,000 Hz

(0,500 s on | 0,500 s off)

15

Alternating 554/440 Hz@ 1,000 Hz

(0,500 s f1 | 0,500 s f2)

16

Alternating 554.440 Hz® 2,000 Hz

(0,100 sf1 | 0,400 sf2)

17

Alternating 800.’1000 Hz @ 4,000 Hz

(0,125 Sf1 | 0,125 s 12)

18

Alternating 800/1000 Hz @ 0,875 Hz

(0,571 s f1 | 0,571 s 12)

19

Alternating 2400/2900 Hz @ 2,000 Hz

(0,250 s f1 | 0250 s f2)

20

Sweeping 500/1200 Hz @ 0,300 Hz

(1,667 s rise | 1,667 s fall)

21

Sweeping 800.-1000 Hz @ 1,000 Hz

(0,500 s rise | 0,500 s fall)

22

Sweeping 800/1000 Hz @ 7,000 Hz

(0,071 s rise | 0,071 s fall)

23

Sweeping 800/1000 Hz @ 50,00 Hz

(0,010 s rise | 0,010 s fall)

24

Sweeping 1200/500 Hz @ 1,000 Hz

(1,000 s fall | 0,000 s rise)

25

Sweeping 1400/1600 Hz @ 0,667 Hz

(1,000 s rise | 0,500 s fall)

26

Sweeping 2400/2900 Hz 1,000 Hz

(0,500 s rise | 0,500 s fall)

27

Sweeping 2400/2900 Hz @ 7,000 Hz

(0,071 s rise | 0,071 s fall)

28

Sweeping 2400/2900 Hz @ 50,00 Hz

(0,010 s rise | 0,010 s fall)

29

Slow Whoop 500/1200 Hz © 0,300 Hz

(2,833 s rise | 0,000 s fall | 0,500 s off)

30

Slow Whoop 500/1200 Hz © 0,267 Hz

(3,500 s rise | 0,000 s fall | 0,250 s off)

31

Siren   830 

Hz

(4,720 siren | 48,96 s hold | 4,725 fall | 10,00 s off)

0 Maximum volume
1 Attenuated volume

-10 dB (A)

2 Attenuated volume

-20 dB (A)

3 Attenuated volume

-30 dB (A)

Volume

Содержание DEV20

Страница 1: ...DEV20 Sounder Technical Manual Eaton MEDC technical manual...

Страница 2: ...N VERTRAG DEFINIERTEN JEDER DIESER VERTR GE BENENNT ALLE PFLICHTEN VON EATON DER INHALT DES VORLIEGENDEN DOKUMENTS WIRD NICHT TEIL EINES VERTRAGES ZWISCHEN DEN PARTEIEN UND NDERT DIESEN AUCH NICHT In...

Страница 3: ...tion 4 Start up 4 Setting of volume and signal tone 5 ISO 9001 5 Recycling 5 Safety instructions 5 Attention ex area 5 Care and maintenance 5 Technical Specifications 5 Terminal room 6 Operating contr...

Страница 4: ...and the conformity declarations on our Website Dimensions Construction The ExII Sounder consists of a compression proof housing with aluminium alloy and a sound channel of impactresistant polyester T...

Страница 5: ...are of the disposal conditions of the specific country Safety instructions Please read this manual and observe the country specific assembly standards as well as the valid safety instructions and acci...

Страница 6: ...M lheim an der Ruhr PTB 12 ATEX 1014 IECEx PTB 13 0012 II 2 G Ex d e IIB H2 T6 Gb Ex d e IIB H2 T6 Gb II 2 D Ex tb IIIC T85 C Db Ex tb IIIC T85 C Db 50 C Ta 60 C Ui Art no F no Information variable WA...

Страница 7: ...cting clamps in the terminal compartment Extern circuitry 1 Signal stage switch S open 2 Signal stage switch S closed Connecting clamps in the terminal compartment Extern circuitry 1 Signal stage swit...

Страница 8: ...ntermittent 2400 Hz 1 000 Hz 0 500 s on 0 500 s off 15 Alternating 554 440 Hz 1 000 Hz 0 500 s f1 0 500 s f2 16 Alternating 554 440 Hz 2 000 Hz 0 100 sf1 0 400 sf2 17 Alternating 800 1000 Hz 4 000 Hz...

Страница 9: ...rical systems and devices must be taken 6 The device may be operated solely under the stated ambient conditions Unfavourable ambient conditions can lead to damage of the device and thus present a pote...

Страница 10: ...t rke und des Signaltones 12 ISO 9001 12 Recycling 12 Sicherheitshinweise 12 Achtung Ex Bereich 12 Wartung und Pflege 12 Technische Daten 12 Technische Daten 13 Anschlussraum 13 Bedienelemente im d Ra...

Страница 11: ...kl rung und den Konformit tserkl rungen auf unserer Website Ma zeichnung Aufbau Der ExII Schallgeber besteht aus einem druckfesten Geh use aus Aluminiumlegierung und einer Schallf hrung aus schlagfest...

Страница 12: ...Elektronik separat zu entsorgen In jedem Fall sind die Entsorgungsbedingungen des jeweiligen Einsatzlandes zu beachten Sicherheitshinweise Lesen Sie bitte diese Betriebsan leitung und beachten Sie die...

Страница 13: ...ngsaufnahme max 14 W AC Ue 85 VAC 264 VAC berspannungskategorie II DC Ue 24 VDC 20 19 2 VDC 28 8 VDC Anschlussklemme Bemessungsquerschnitt bis 2 5 mm2 Mehrleiteranschluss max 2 x 1 mm2 Anzugsdrehmomen...

Страница 14: ...14 DEV20 Sounder Technical Manual DEV20 SOUNDER TECHNICAL MANUAL TMF0047 A www eaton com Bedienelemente im d Raum Lautst rke Messmethode...

Страница 15: ...haltung 1 Signalstufe Schalter S offen 2 Signalstufe Schalter S geschlossen Schallgeber f r Wechselspannung Montage Set Die ordnungsgem e Erdung und Montage des Ger tes ist nach EN 60728 11 VDE 0855 1...

Страница 16: ...eeping 2400 2900 Hz 7 000 Hz 0 071 s rise 0 071 s fall 28 Sweeping 2400 2900 Hz 50 00 Hz 0 010 s rise 0 010 s fall 29 Slow Whoop 500 1200 Hz 0 300 Hz 2 833 s rise 0 000 s fall 0 500 s off 30 Slow Whoo...

Страница 17: ...kpr fung f r das Ger t durchgef hrt werden 8 Reinigunsarbeiten d rfen wegen der Gefahr elektrostatischer Aufladung nur mit einem feuchten Tuch erfolgen 9 Es d rfen nur die vom Hersteller vorgeschriebe...

Страница 18: ...alit s de signal 20 ISO 9001 20 Recyclage 20 Consignes de s curit 20 Pr cautions relatives aux zones Ex 20 Entretien et maintenance 20 Caract ristiques techniques 20 Espace de raccordement des bornes...

Страница 19: ...tion de conformit jointe et les d clarations de conformit disponibles sur notre site Web Dimensions Construction La sir ne ExII est constitu e d un bo tier r sistant la pression en alliage d aluminium...

Страница 20: ...s tous les cas veuillez prendre connaissance des conditions de mise au rebut du pays concern Consignes de s curit Veuillez lire ce manuel et respecter les normes d assemblage sp cifiques au pays ainsi...

Страница 21: ...12 ATEX 1014 IECEx PTB 13 0012 II 2 G Ex d e IIB H2 T6 Gb Ex d e IIB H2 T6 Gb II 2 D Ex tb IIIC T85 C Db Ex tb IIIC T85 C Db 50 C Ta 60 C Ui R f N F Informations variables AVERTISSEMENT NE PAS OUVRIR...

Страница 22: ...cordement des bornes Circuit externe 1 Niveau de signal interrupteur S ouvert 2 Niveau de signal interrupteur S ferm Bornes de raccordement dans l espace de raccordement des bornes Circuit externe 1 N...

Страница 23: ...he de 0 500 s arr t de 0 500 s 15 Alternance 554 440 Hz 1 000 Hz f1 pendant 0 500 s f2 pendant 0 500 s 16 Alternance 554 440 Hz 2 000 Hz f1 pendant 0 100 s f2 pendant 0 400 s 17 Alternance 800 1 000 H...

Страница 24: ...isation de syst mes et d appareils lectriques doivent tre suivies 6 L appareil ne doit tre utilis que dans les conditions ambiantes indiqu es Des conditions ambiantes d favorables peuvent endommager l...

Страница 25: ...ed in this document and to prices are reserved so are errors and omissions Only order confirmations and technical documentation by Eaton is binding Photos and pictures also do not warrant a specific l...

Отзывы: