6 Parameter structure
6.6 Parameter
142
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
6.6 Parameter
The following tables use a number of acronyms. These acronyms are defined
below:
6.6.1 “Monitor” parameter group
Table 47: “Monitor” parameter group
Abbreviation
Meaning
Min. value
Minimum value
Max. value
Maximum value
DS
Default setting (the parameter’s value when using the device’s
factory settings)
→
None of the parameters in parameter group 0 can be modified
by the user, i.e., they are read-only parameters.
Parameter
Designation
min. value
max. value
Description
P00-01
Analog Input1
0
100%
Analog Input 1
Level of the signal applied to analog input 1 after
scaling and offsets have been applied.
P00-02
Analog Input2
0
100%
Analog Input 2
Level of the signal applied to analog input 2 after
scaling and offsets have been applied.
P00-03
Frequency Reference
-P-01
P-01
Frequency Reference in Hz.
Will be calculated into rpm when motor data are
available.
Value of the drive internal digital reference.
P00-04
DI1 Status
0
1
State of digital inputs
Status of the digital inputs starting on the left hand
side with digital input 1 etc.
DI2 Status
0
1
DI3 Status
0
1
DI4 Status
0
1
DI5 Status
0
1
P00-05
PID1 Output
0
100 %
PI(D) controller 1 Output
P00-06
DC-Link Voltage Ripple
0
1000 V
DC-Link Voltage Ripple
P00-07
Motor voltage
0 V
600 V AC
Instantaneous output voltage
P00-08
DC Link Voltage
0 V
1000 V DC
Instantaneous DC Link Voltage
P00-09
Heatsink Temperature
-20 °C
100 °C
Instantaneous Heatsink Temperature
P00-10
t-Run
0 h
99999 h
Total operating time of the drive since the date of
manufacture
P00-11
t-Run since Trip
0 h
65000 h
Total operating time of the drive since the last trip
occurred
Содержание DC1-S1011NB-A20CE1 1
Страница 4: ......
Страница 124: ...5 Operation 5 7 Handling the keypad 120 DC1 S 20 DC1 S OE1 Variable Frequency Drives 05 21 MN040058EN www eaton com...
Страница 160: ...6 Parameter structure 6 7 Fault messages 156 DC1 S 20 DC1 S OE1 Variable Frequency Drives 05 21 MN040058EN www eaton com...
Страница 170: ...7 Technical Data 7 3 Dimensions 166 DC1 S 20 DC1 S OE1 Variable Frequency Drives 05 21 MN040058EN www eaton com...