The horn – DB3B UL

   TM261   April 2020   www.eaton.com

The horn – DB3B UL

English

Wiring details

The unit is available in a number of basic configurations:

1.  AC input, single stage.
2.  AC input, dual stage with voltage-free stage selection.
3.  DC input, up to 3 user selectable stages without 

monitoring.

4.  DC input, up to 2 user selectable stages with 

EOL/monitoring (standard configuration).

5.  DC input, up to 3 user selectable stages with 2 

independantly powered stages.

6.  DC input, up to 3 user selectable stages with optional 

EOL/monitoring (alternative configuration).

7.  DC input, 5 user selectable stages with voltage free 

stage selection with or without monitoring.

AC version wiring details (Types 1 & 2)

•  Type 1:

 Connect the live and neutral supply wires to 

the terminals as detailed in the wiring diagram. The 

unit will be supplied with the link between R1 and R0 

fitted to the terminals. When power is applied to the 

unit, the stage 1 tone will be produced as selected 

on the 5- way DIP switch.

•  Type 2:

 Connect the live and Neutral supply wires 

to the terminals as detailed in the wiring diagram. 

The unit will be supplied with no link fitted between 

R1 and R0. Connect wires and remote switches to 

terminals R0, R1 and R2 as shown. When power is 

initially applied to the unit, no tone will be produced. 

When the switch connected to R1 is closed, the 

stage 1 tone will be produced as selected by the 

5-way DIP switch on the electronics assembly. 

When the switch connected to R2 is closed, the 

pre-selected tone for stage 2 is produced. See tone 

table 2 for details of pre-selected tones.

ote: 

N

Closing both switches will produce no tone.

DC version – 3 stage without monitoring wiring 

details (Type 3)

This type can be configured in a number of different ways 

depending on requirements. Independent tone selection 

for all 3 stages is via the 3 off 5-way DIP switches fitted 

to the electronics assembly:

•  2-wire system (Single stage):

 Connect the positive 

and negative supply wires to the terminals as detailed 

in the wiring diagram.

•  2-wire system (Dual stage, reverse polarity):

 

Connect the positive and negative supply wires to 

the terminals as detailed in the wiring diagram. The 

second stage is produced by reversing the polarity of 

the supply to the unit.

•  3-wire system (Dual stage, ve):

 Connect 

3 supply wires to the terminals as detailed in the 

wiring diagram (1 ve wire and 2 -ve wires). 

Stage 1 is produced when power is applied across the 

ve and stage 1 -ve terminals. Stage 2 is 

produced when power is applied across the common 

+ve and stage 2 -ve terminals.

•  3-wire system (Dual stage, common -ve):

 Connect 

3 supply wires to the terminals as detailed in the 

wiring diagram (2 +ve wires and 1 common -ve wire). 

Stage 1 is produced when power is applied across 

the stage 1 +ve and common -ve terminals. Stage 2 

is produced when power is applied across the stage 2 

+ve and stage common -ve terminals.

•  4-wire system (Triple stage, Common -ve):

 Connect 

4 supply wires to the terminals as detailed in the 

wiring diagram (3 +ve wires and 1 common -ve wire). 

Stage 1 is produced when power is applied across 

the stage 1 +ve and common -ve terminals. Stage 2 

is produced when power is applied across the stage 2 

+ve and common -ve terminals. Stage 3 is produced 

when power is applied across the stage 3 +ve and 

common -ve terminals.
All versions are supplied with terminals to allow 

loop-in loop-out connection of the supply wires.

Содержание DB3B UL

Страница 1: ...The horn DB3B UL Technical manual...

Страница 2: ...URPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL...

Страница 3: ...ard configuration wiring details Type 4 3 DC Version Up to 3 user selectable stages with 2 independantly powered stages Type 5 3 DC version Up to 3 stage with or without monitoring alternative configu...

Страница 4: ...iv The horn DB3B UL TM261 April 2020 www eaton com...

Страница 5: ...Ensure that only the correct listed or certified stopping plugs are used to blank off unused gland entry points and that the NEMA IP rating of the unit is maintained X MEDC recommend the use of a seal...

Страница 6: ...es will produce no tone DC version 3 stage without monitoring wiring details Type 3 This type can be configured in a number of different ways depending on requirements Independent tone selection for a...

Страница 7: ...s M1 M2 terminals ote N monitored terminals are not polarity dependent DC Version Up to 3 user selectable stages with 2 independantly powered stages Type 5 Connect up to 4 supply wires to the terminal...

Страница 8: ...ation wiring details Type 7 Connect the positive ve and negative ve supply wires to the terminals as detailed in the wiring diagram When power is applied to the unit no tone will be produced initially...

Страница 9: ...01101 Swedish Fire Alarm 20 Alt 554 440 Hz at 1 Hz 01100 Swedish Fire Alarm 21 Int 660 Hz at 7 8 Hz 01011 Swedish Fire Alarm 22 Int 2850 Hz 150 mS on 100 mS off 01010 Pelican Crossing 23 Sweep 800 970...

Страница 10: ...T14 T10 T1 T8 T14 26 3x2850Hz pulses 0 5on 0 5off 1 5 off 00110 T14 T10 T1 T8 T14 27 Int 3100Hz 0 32s on 0 68s off 00101 T14 T10 T1 T8 T14 28 Continuous 1400Hz 00100 T14 T10 T1 T8 T14 29 Spare Custom...

Страница 11: ...A Angle OSPL dBA Long Flare Version Horizontal Axis Reference 90 93 9 Reference 90 C 93 9 165 90 9 3 dBA 20 90 9 3 dBA 87 9 6 dBA 87 9 6 dBA 180 92 0 0 91 9 Long Flare Version Vertical Axis Reference...

Страница 12: ...etal products However if abnormal or unusual environmental conditions occur due to plant damage or accident etc then visual inspection is recommended If the unit requires cleaning then only clean exte...

Страница 13: ...0 Hz 122mA Special Applicaton 3 120 V ac 50 60 Hz 110 mA Regulated 4 220 230 Vac 50 60 Hz 63 mA Special Application 5 240 Vac 50 60 Hz 58 mA Regulated Note the DC special application version is suitab...

Страница 14: ...der is intended for use in a safety system conforming to the requirements of IEC61508 UL has conducted a Failure Modes Effect and Diagnostic Analysis FMEDA of the DB3B Sounder against the requirements...

Страница 15: ...for use in safety functions and the installation configuration overall validation maintenance and repair shall only be carried out by competent personnel observing all the manufacturer s conditions a...

Страница 16: ...ard type 4 16 Version CC Jusqu 3 tages s lectionnables par l utilisateur avec 2 tages aliment s ind pendamment type 5 16 D tails du c blage version CC Jusqu trois tages avec ou sans surveillance confi...

Страница 17: ...u certifi s doivent tre utilis s IX S assurer que seul les bouchons r pertori s corrects ou certifi s sont utilis s pour obturer les points d entr e des presse toupes inutilis s et que l indice IP NEM...

Страница 18: ...teurs ne produira aucun son D tails du c blage version CC Trois tages sans surveillance type 3 Ce type peut tre configur de plusieurs mani res diff rentes en fonction des besoins La s lection ind pend...

Страница 19: ...nes surveill es ne sont pas d pendantes de la polarit Version CC Jusqu 3 tages s lectionnables par l utilisateur avec 2 tages aliment s ind pendamment type 5 Branchez jusqu 4 fils d alimentation aux b...

Страница 20: ...e d taill dans le sch ma de c blage L tage 1 est produit quand l alimentation est appliqu e entre les bornes du commun VE et VE de l tage 1 L tage 2 est produit quand l alimentation est appliqu e entr...

Страница 21: ...12 48 V CC la gamme de tension d entr e absolue est de 11 0 V CC 58 0 V CC L unit est quip e d une commande de volume qui est positionn e sur la partie sup rieure de la platine du circuit imprim Le v...

Страница 22: ...dant 0 1 S 440 Hz pendant 0 4 S 10001 Tonalit d incendie fran aise 16 Int 660 Hz 150 ms on 150 ms off 10000 Tonalit d incendie su doise 17 Int 660 Hz 1 8 sec on 1 8 sec off 01111 Tonalit d incendie su...

Страница 23: ...T8 T14 16 Int 660 Hz 150 ms on 150 ms off 10000 T14 T10 T1 T8 T14 17 Int 660Hz 1 8 sec on 1 8 sec off 01111 T14 T10 T1 T8 T14 18 Int 660Hz 6 5 sec on 13 sec off 01110 T14 T10 T1 T8 T14 19 Continue 66...

Страница 24: ...9 3 dBA 46 86 9 3 dBA 148 83 9 6 dBA 35 83 9 6 dBA 180 81 8 0 81 5 Axe vertical en version courte vas e R f rence 90 89 8 R f rence 90 89 8 143 86 8 3 dBA 47 86 8 3 dBA 150 83 8 3 dBA 35 83 8 6 dBA 18...

Страница 25: ...es Toutefois si des conditions environnementales anormales ou inhabituelles se produisent en raison de dommages l installation ou d accident etc alors un contr le visuel est recommand Si l unit n cess...

Страница 26: ...sez au minimum des c bles class s 105 C 6 Avertissement sur les unit s peintes pour viter l accumulation de charges lectrostatiques nettoyer le bo tier avec un chiffon humide 7 Avertissement afin de r...

Страница 27: ...ettre l int grit de s curit de l quipement valu 1 L utilisateur est tenu de se conformer aux exigences nonc es dans la documentation utilisateur fournie par le fabricant ce Manuel de s curit et Manuel...

Страница 28: ...n contained in this document and to prices are reserved so are errors and omissions Only order confirmations and technical documentation by Eaton is binding Photos and pictures also do not warrant a s...

Отзывы:

Похожие инструкции для DB3B UL