background image

Operations and Maintenance Manual 

for Eaton Pressure Filters, Change-Over 
DA/EDA 103,253,403,633,1003, related specification

 

Sheet No. 

67630-4D 

 

Page  2/4

 

 

 

 

 

 

When fastening the counter flanges, use the torque values in the table below.  Ensure faces are parallel 
before fastening connections.  

 

Type 

DA/EDA 103 

DA/EDA 253, 403 

DA/EDA 633, 1003 

Connection 

1“ (DN25) 

2“ (DN50) 

3“ (DN80) 

Torque Nm 

lbf.-ft. 

 

10 

2  

.08 

 

28 

21 

.24 

 

71 

15 

52 

.56 

 

 
 

3. Commissioning 

Ensure the filter installation is complete and the system is clean before commissioning. Follow these 
instructions to purge the filter before commissioning the system: 

 

1.  Before commissioning, ensure that the filter element and seals are clean and properly installed. 
2.  Place the switchgear lever in the middle position. 
3.  Fill both sides of the filter housing at the regular operating fluid flow. 
4.  Open  the  air  bleed  screws  or  connections.  Connect  tubes  that  lead  to  a  drain  pan  (air-bleed 
 

connection information can be found on data sheet 1659). 

5.  Allow the operating fluid to drain (reduce volume flow from 10 to 50 l/min (2.6 to 13.2 GPM))

 

until 

 

it is bubble-free and flows out of both air bleeding tubes.) 

6.  Shut off application flow. 
7.  Remove the air bleeding tubes and close the air-bleed bore holes or air-bleed connections. 
8.  Switch to the filter housing you would like to operate first by using the switch gear lever. 
9.  After finishing step 7, tighten the locking screws.

 

 

After following these instructions for commissioning, the serviced filter vessel is ready for operation.

 

 
 

DA/EDA 103-1003 (illustration can slightly differ for different sizes) 

 

 

1)  Connection for the potential equalization, 

only for application in the explosive area. 

 

Fitting the counter flanges

 

 

Содержание DA/EDA 103

Страница 1: ... pressure and high temperatures This does not apply to the offline vessel that is not under operation FAILURE TO FOLLOW THIS WARNING COULD LEAD TO DEATH SEVERE INJURY OR PROPERTY DAMAGE WARNING Leaking operating fluid can cause injury and burns Equipment should be shut down and isolated from energy sources and other equipment before any inspection or servicing to prevent risk of shock or process f...

Страница 2: ...tion 3 Fill both sides of the filter housing at the regular operating fluid flow 4 Open the air bleed screws or connections Connect tubes that lead to a drain pan air bleed connection information can be found on data sheet 1659 5 Allow the operating fluid to drain reduce volume flow from 10 to 50 l min 2 6 to 13 2 GPM until it is bubble free and flows out of both air bleeding tubes 6 Shut off appl...

Страница 3: ...r lid back onto the filter housing and tighten the screw plugs The screws need to be tightened in an X pattern Recommended tightening torques listed in the table below Type DA EDA 103 DA EDA 253 403 DA EDA 633 1003 Screw M10 M12 M16 Torque Nm lbf ft 45 50 33 37 65 70 48 52 125 130 92 96 11 Close the drain plugs 12 Open the pressure balance valve until operating fluid flows out of the air bleed con...

Страница 4: ...e effects of such use or the results to be obtained Eaton assumes no liability arising out of the use by others of such products Nor is the information herein to be construed as absolutely complete since additional information may be necessary or desirable when particular or exceptional conditions or circumstances exist or because of applicable laws or government regulations EN 11 2019 6 Pressure ...

Отзывы: