3
Instruction Leaflet IL
66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
EATON CORPORATION www.eaton.com
I.L. 66A7638H03
Effective September 2007
3
1.0
GENERAL DESCRIPTION
The DNP MINT (DNP Master INCOM Network
Translator) Module, as seen in
Figure 1
, is a
Eaton Electrical accessory product that will
provide communication between a DNP 3.0
network master and an INCOM (INdustrial
COMmunications) network of MPCV Relays
(see
Figure 2
). The module is transparent to the
DNP network master. It communicates to a
master on the DNP network using the DNP 3.0
protocol. It communicates to slave devices on
the INCOM network using the IMPACC
(Integrated Monitoring, Protection, And Control
Communication) protocol.
2.0
FEATURES
The DNP MINT module is a slave device on the
DNP network and as such requires a master that
will poll/accept DNP objects from the DNP
MINT module.
•
DNP communications data transfer rates of
1200, 9600, or 19200 baud with 1 start bit, 8
data bits, no parity and either one or two
stop bits.
•
Up to 16 devices such as the MPCV Relay
connected to the INCOM network port.
•
Flashing Status LED to indicate an active
module.
•
LED indicators for DNP RS-485 transmit
and receive communications exchanges.
•
LED indicators for INCOM transmit and
receive communications exchanges.
•
Input power for the module from either 120
VAC or 24 to 125 VDC.
•
DIN rail mount package.
•
-40ºC to 85ºC ambient operation.
3.0
INSTALLATION
The DNP MINT module is designed to be
installed, operated and maintained by adequately
trained personnel. These instructions do not
cover all of the details or variations of the
equipment for its storage, delivery, installation,
checkout, safe operation or maintenance. When
mounting the DNP MINT verify that a “C”
Shape
32mm
or Standard
35/7.5mm DIN Rail
is used and that it is within an enclosed space.
WARNING
DO NOT ATTEMPT TO INSTALL OR
PERFORM
MAINTENANCE
ON
EQUIPMENT WHILE IT IS ENERGIZED.
DEATH OR SEVERE PERSONAL INJURY
CAN RESULT FROM CONTACT WITH
ENERGIZED EQUIPMENT. ALWAYS
VERIFY THAT NO VOLTAGE IS
PRESENT
BEFORE
PROCEEDING.
ALWAYS
FOLLOW
SAFETY
PROCEDURES. EATON ELECTRICAL
INC. IS NOT LIABLE FOR THE
MISAPPLICATION
OR
MISINSTALLATION OF ITS PRODUCTS.