SPI9000 Inverter Unit FI9 – FI14 User Manual
MN04004002E
For more information visit:
www.EatonElectrical.com
3-11
September 2006
Inverter Supply and Motor Cables — 380 – 500V AC
Table 3-4: Cable Sizes for 380 – 500V AC
Flexible conductor. Minimum temperature endurance for isolation 70°C.
Copper busbar.
The modules require symmetrical parallel cable with minimum length 40m or dU/dt- or sinus filter.
Table valid for enclosure class IP20 cabinets.
Motor cables — EN 60204-1, IEC 60364-5-2/2001
–
PVC insulation
–
40°C ambient temperature
–
70°C surface temperature
Nominal
Current
Frame
I
L
[A]
Module Supply (DC)
(per terminal Cu [mm
2
]
Motor Cable
[mm
2
]
140
FI9
170
2x(1x24)
Cu: 3x95+50
Al: 3x120+70
170
205
2x(1x24)
Cu: 3x150+70
Al: 72Cu
205
261
3x(1x24)
Cu: 3x185+95
Al: 2x(3x120+70)
245
300
6x(1x24)
Cu: 2x(3x120+70)
Al: 2x(57Cu)
300
FI10
385
5x40
Cu: 2x(3x120+70)
Al: 2x(57Cu)
385
460
5x40
Cu: 2x(3x150+70)
Al: 2x(72Cu)
460
520
6x40
Cu: 2x(3x185+95)
Al: 2x(88Cu)
520
FI12
590
5x40
Cu: 2x(3x240+120)
Al: 4x(41Cu)
590
650
5x40
Cu: 4x(3x95+50)
Al: 4x(41Cu)
650
730
5x40
Cu: 4x(3x120+70)
Al: 4x(57Cu)
730
820
5x40
Cu: 4x(3x150+70)
Al: 4x(57Cu)
820
920
5x40
Cu: 4x(3x150+70)
Al: 4x(72Cu)
920
1030
6x40
Cu: 4x(3x185+95)
Al: 4x(88Cu)
1030
FI13
1150
5x40
Cu: 4x(3x240+170)
Al: 6x (57Cu)
1150
1300
5x40
Cu: 6x(3x150+70)
Al: 6x (70Cu)
1300
1450
6x40
Cu: 6x(3x185+95)
Al: 6x (70Cu)
1600
FI14
1770
5x40
Cu: 2x 4x(3x240+170)
Al: 2x 6x (57Cu)
1940
2150
5x40
Cu: 2x 6x(3x150+70)
Al: 2x 6x (70Cu)
2300
2700
6x40
Cu: 2x 6x(3x185+95)
Al: 2x 6x (70Cu)