Figure 9-20: Stall Characteristics Settings
Figure 9-21: Stall Time Count
2.7.12 Stall current limit
ID710
The current can be set to 0.0 – I
nMotor
*
2. For a stall stage to occur, the current must
have exceeded this limit. See
Figure 9-20
. The software does not allow entering a
greater value than I
nMotor
*
2. If the parameter 2.1.9 Nominal current of motor is
changed, this parameter is automatically restored to the default value (I
nMotor
*
1.3).
2.7.13 Stall time
ID711
This time can be set between 1.0 and 120.0s.
This is the maximum time allowed for a stall event detection. The stall time is
counted by an internal up/down counter.
If the stall time counter value goes above this limit, the protection will cause a trip
(see
Figure 9-21
).
S
tall Area
Par. ID710
Par. ID712
f
I
S
tall Time Cou
n
ter
Trip Area
Par. ID711
S
tall
No
S
tall
Time
Trip/ War
n
i
n
g
Par. ID709
Содержание Cutler-Hammer SLX9000 Series
Страница 1: ...SLX9000 Adjustable Frequency Drives User Manual Effective January 2009 Supersedes October 2008...
Страница 2: ......
Страница 110: ...SLX9000 Adjustable Frequency Drives User Manual 8 18 For more information visit www eaton com MN04003020E January 2009...
Страница 164: ...SLX9000 Adjustable Frequency Drives User Manual A 4 For more information visit www eaton com MN04003020E January 2009...
Страница 166: ...SLX9000 Adjustable Frequency Drives User Manual B 2 For more information visit www eaton com MN04003020E January 2009...
Страница 168: ...SLX9000 Adjustable Frequency Drives User Manual C 2 For more information visit www eaton com MN04003020E January 2009...
Страница 171: ......