Short Circuit Protection by Fuses

Type 1

S701X25N3BP — protection max. 80A 

g

I/

g

L/

g

G 63A T

Type 2

S701X25N3BP — protection max. I

2

t of the fuse 6300A

2

S

NOTE: S701X25N3BP

 — When protected by H class fuses, 

this device is rated for use on a circuit capable of 
delivering not more than 5000 rms symmetrical 
amperes, 600V maximum.

How to Adjust Time and Torque, Figure 10

The Soft Starter will read time and torque settings in the OFF 
state. Repeated starts may trip the motor protection relay. DO 
NOT set the rotary switches in between positions. This cor-
rupts the time and torque adjustment. Use screwdriver 2 mm x 
0.5 mm.

Ramp-Up Time and Initial Torque

Table 8. 

Ramp-Up Time and Initial Torque

(Standard Load) 

Kick Start/Break Loose

If it is not possible to reach a time sufficient for the application, 
it may be necessary to kick start the load.

Table 9. 

Kick Start/Break Loose (High Inertia Loads)

Ramp-Down Time

Follow 

Table 8

 to set 

Ramp-Up

 and 

Initial Torque

Table 10. 

Ramp-Down Time, e.g. Pump Loads 

Figure 10. 

Time and Torque Adjustment

Position

Setting/Adjustment

Set the 

Ramp-Up

 switch to maximum.

Set the 

Ramp-Down

 switch to minimum.

Set the 

Initial Torque 

switch to minimum.

Apply control signal for a few seconds. If the load does not 
rotate immediately, increment the 

Initial Torque

 and try 

again. Repeat until the load starts to rotate immediately on 
startup.

Adjust 

Ramp-Up

 time to the estimated start time (the 

scale is in seconds) and start the motor.

Decrease the 

Ramp-Up

 time until mechanical surge is 

observed during start.

Increase the time one step to eliminate the surge.

Position

Setting/Adjustment

Set the 

Ramp-Up

 switch to maximum.

Set the 

Ramp-Down

 switch to minimum.

Set the 

Initial Torque 

switch to minimum kick 

start torque.

Apply control signal for a few seconds. If the load stops 
right after the 200ms “kick”, increment the

 Initial Torque

 

and try again. Repeat until the load continues to rotate 
after the “kick”. 

Adjust 

Ramp-Up

 time to the desired start time (the scale is 

in seconds) and start the motor.

Position

Setting/Adjustment

Set the 

Ramp-Down

 switch to maximum.

Switch off the control voltage and observe any mechanical 
surges on the load. If there are none, decrement 

Ramp-

Down

 switch and try again. Repeat until mechanical surge 

on the load is observed.

Increase the time one step to eliminate the surge.