on the front of the relay, via the two display windows. This 
is considered “ON DEVICE” information.  
 
In addition to being able to provide a circuit breaker 
“OPEN” or “CLOSED” status to the remote location, the 
MD-3000 displays parameters, such as: 
 

• 

Individual phase differential currents 

• 

Magnitude and phase of current causing trip 

• 

Cause of trip 

• 

Current transformer ratio 

• 

Existing set point settings 

• 

Software Version 

 

1-4 STANDARDS 

MD-3000 Protective Relays are “Component Recognized” 
by the Underwriters Laboratory, Inc.® under UL File 
E154862. Refer to Section 2-3 UL Testing and 
Specification Summary for more information. 

SECTION 2: FUNCTIONAL DESCRIPTION 

2-1 PROTECTION, SETTINGS, AND TESTING 

2-1.1 RMS SENSING 

MD-3000 Protective Relays provide true RMS sensing for 
proper correlation with the thermal characteristics of 

conductors and equipment. The root-mean-square (rms) 
value is determined by a microprocessor calculation of 
discrete sampled points of the current waveform. This rms 
value is used for the protection response and metering 
displays of the relay.  

2-1.2 PICKUP SETTING 

A MD-3000 Protective Relay pickup setting is a discrete, 
pre-selected value of differential current used to initiate a 
tripping action. The available pickup settings are 0.04, 
0.06, 0.08, 0.10, 0.12, 0.14, 0.16, 0.18, 0.20, 0.22, 0.24, 
0.26, 0.28, 0.30, 0.32, 0.34, 0.36, 0.38, 0.40, 0.42, 0.44, 
0.46, 0.48, 0.50, and NONE. 
 

2-1.3 TIME SETTING 

A MD-3000 Protective Relay time setting is a pre-selected 
time delay initiated when the pickup is exceeded. If the 
current value drops below the pickup value, the timing 
function resets.  Memory is NOT provided. If the current 
value does not drop below pickup, the amount of delay 
before tripping occurs is a function of only the time setting.  
The available time settings are 0.05, 0.10, 0.15, 0.20, 0.25, 
0.30, 0.35, 0.40, 0.45, 0.50, 0.55, 0.60, 0.65, 0.70, 0.75, 
0.80, 0.85, 0.90, 0.95, 1.00, 1.25, and 1.50 (seconds).  

2-1.4 MISCELLANEOUS SETTINGS 

 

TABLE 2.1 MISCELLANEOUS SETTINGS 

TYPE SETTING 

AVAILABLE SETTINGS 

FREQUENCY  

50 Hz, 60 Hz 

PHASE CT RATIO  

5,10, 25, 50, 75,100,150, 200, 250, 300, 400, 500, 600, 630, 
800, 1000, 1200, 1250, 1500, 1600, 2000, 2400, 2500, 
3000,3200, 4000, 5000  

TEST 

Phase 

 

Phase Trip 

 

 

 
P1, P2, P3, P4, P5, P6, P7, P8, P9, P10, P12, P14, P16 
P18, P20, P22, P25 
 
P3T, P10T, P25T 
 
 

 

 

System Frequency Selection: 

Either 60Hz or 50Hz may 

be selected. 
 

Phase CT Ratio Selection: 

The available CT ratios, 

shown in the above table range from 5:5 to 5000:5. 

 
Defaults: 

In the unlikely event that settings are missed or 

entered incorrectly, the Operational LED will blink Red and 
the relay will display “PRGM” in the Settings Display 
window. This means the program settings should be re-
entered and saved. 

2-1.5 TESTING 

Phase no-trip tests (test Px) and a phase trip tests (PxT) 
are provided (see table 2.1). 
 

 

THE TEST MODE SHOULD NOT BE USED TO 
TRIP LIVE CURRENT CARRYING CIRCUITS. IF A 
LIVE CURRENT OF GREATER THAN 0.1 TIMES 
THE VALUE IS FLOWING IN ANY PHASE, THE 
TEST MODE IS AUTOMATICALLY EXITED, 
ACCOMPANIED BY AN ERROR MESSAGE IN THE 
SETTINGS/TEST TIME/TRIP CAUSE WINDOW. 

 

2-2 PROTECTIVE RELAY HARDWARE 

2-2.1 FRONT OPERATIONS PANEL 

The operations panel, which is normally accessible from 
the outside of the switchgear panel door, provides a 
means to program, monitor and test the unit (Figure 1-1). 

Содержание CUTLER-HAMMER MD-3000 series

Страница 1: ...Effective March 2006 Initial Release per IQ 10256 IB02602001E INSTRUCTIONS FOR INSTALLATION OPERATION AND MAINTENANCE OF THE CUTLER HAMMER MD 3000 SERIES OF PROTECTIVE RELAYS...

Страница 2: ...Effective March 2006 Initial Release per IQ 10256...

Страница 3: ...TECTIVE RELAY HARDWARE 2 2 1 FRONT OPERATIONS 2 2 2 Rear Access Panel 2 2 3 EXTERNAL SECTION 3 OPERATION 3 1 INTRODUCTION 3 2 POWER UP AND SELF TESTING 3 3 PANEL OPERATIONS 3 4 TEST MODE SECTION 4 INS...

Страница 4: ...YLES LISTED IN TABLES 1 1 AND 1 2 This document is provided as a guide for authorized and qualified personnel only Please refer to the specific CAUTION in Section 1 1 2 before proceeding If further in...

Страница 5: ...ly one relay is required per three phase circuit An integral part of each device is the differential current monitoring and the ability to select protective functions THE LOSS OF CONTROL VOLTAGE WILL...

Страница 6: ...the pickup is exceeded If the current value drops below the pickup value the timing function resets Memory is NOT provided If the current value does not drop below pickup the amount of delay before tr...

Страница 7: ...ode will automatically exit if there is no activity for approximately 2 1 2 minutes Select Test Pushbutton Yellow The Select Test pushbutton is used after the test mode has been entered to select the...

Страница 8: ...he relay Become familiar with the functions and connections involved especially the following DIP Switches A set of ten DIP switches is located in the upper left portion of the rear panel These switch...

Страница 9: ...RF radiated Immunity to 10V M EN61000 4 4 1995 Electrical Fast Transient Immunity to 10V M IEC 255 22 4 1989 Electrical Fast Transient Immunity to 10V M EN61000 4 5 1995 Surge Immunity 2 1KV C DM EN6...

Страница 10: ...1 2 minutes To enter the Program Mode open the protective access cover and press and release the Program Mode On Off pushbutton The Program LED will blink green indicating that the Program Mode has be...

Страница 11: ...AND TESTING 4 1 INTRODUCTION This section describes mounting wiring startup and miscellaneous testing details associated with the MD 3000 Protective Relay INSURE THAT THE INCOMING AC POWER AND FOREIG...

Страница 12: ...For more information visit www EatonElectrical com Initial Release Fig 4 1 Cutout Dimensions Inches...

Страница 13: ...shown in Figure 3 1 An example of a typical wiring plan is shown in Figure 2 1 Note the following 1 The wires to the terminal blocks must not be larger than AWG No 14 Larger wire will not connect pro...

Страница 14: ...ase Fig 4 3 MD 3000 Typical Wiring Diagram With fault condition shown on phase C Note The above diagram shows a common wiring scheme when the relay is used in conjunction with a breaker The Differenti...

Страница 15: ...in the Replacement section below 5 1 1 STORAGE The MD 3000 Protective Relay should be stored in an environment that does not exceed the specified storage temperature range of 40 C to 70 C The environ...

Страница 16: ...ED OR REMOVED WITHOUT SUCH SUPPORT THE PROTECTIVE RELAY COULD FALL OR THE PANEL COULD BE DAMAGED Step 6 Mount the replacement unit Read the Mounting section of this document before attempting this Ste...

Страница 17: ...ars in Settings Display Window Check sum did not Match Replace Protective Relay if PGRM Reappears After Saving Settings Paragraph 5 3 ERR Appears in Setting There was an Error While in the Test Mode M...

Страница 18: ...lse tripping A3 0 INSTALLATION NOTE Please refer to the following section if you are using the MD 3001 Drawout Relay A3 1 PANEL PREPARATION When mounting the Drawout Case in a panel it is necessary to...

Страница 19: ...com Initial Release Fig A 2 MD 3001 Panel Mounting 18 17 Current Input Unused 29 27 Power Supply B2 C2 A2 Input 23 25 21 19 Unused 30 28 24 26 22 B1 C1 A1 Unused 20 Unused 11 15 13 12 Unused 16 14 Un...

Страница 20: ...E For more information visit www EatonElectrical com Initial Release Caution Refer to Instruction Leaflet AC 120 240 Vac 50 60 Hz MD 3001 Motor Differential Term 17 19 DC 48 250 Vdc Power Supply Input...

Страница 21: ...sides of the device are seated and latched into place Tabs on the MD 3001 Drawout Inner Chassis will prevent the inner chassis from being inserted upside down or being inserted into an enclosure of an...

Страница 22: ...ENT ALWAYS DISCONNECT ANY CONTROL OR SOURCE POWER BEFORE TOUCHING ANYTHING ON THE INTERNAL OR EXTERNAL PARTS OF THE DRAWOUT OUTER CASE When removing the Inner Chassis from the Drawout Outer Case first...

Страница 23: ...A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event...

Отзывы: