2

 

 

     Figure 3 

 
2.4 Wiring  

Power poles can accept wires from #14 to #8 AWG (either 
solid or stranded) as single or combination of two wires (refer 
to Table B below for valid wire combination).  Wire material 
must be copper with a temperature rating of 75 degrees C.  
Maximum tightening torque is 35 in-lbs.  

 

8 AWG 

10 AWG 

12 AWG 

14 AWG 

Size Type 

Stranded Stranded  Solid  Stranded Solid Stranded Solid 

AWG 

Stranded X  X X X X X X 
Stranded X  X X X X X X 

10 AWG 

Solid  X  X X X X X X 

Stranded X  X X X X X X 

12 AWG 

Solid  X  X X X X X X 

Stranded X  X X X X X X 

14 AWG 

Solid  X  X X X X X X 

                                           Table B 

         

   

 

 

3   AUXILIARY CONTACTS:  C320AMH1 & C320AMH2 

 

3.1 Description 

The auxiliary contact blocks are available in both single pole 
(C320AMH1) and double pole (C320AMH2) versions. 

 

Auxiliary contacts can be added on either side of the base (see 
Figure 1). When added to the LEFT side of base, the auxiliary 
block functions as “NO”, and when added to the RIGHT side 
of base it functions as “NC”.   Refer to section 4.3 for wiring. 

 

4   CONTROL MODULE KITS 

The base (electrically held) can be converted to a mechanically 
held type by adding a control module kit.  

 

IMPORTANT

:  The control module kits are for use with the 

coils up to 277 VAC maximum.  Use a control power 
transformer for higher voltages. 

 

Conversion from an electrically held to a mechanically held 
type is possible by adding a “control module kit” to the base. 

 

4.1  Description 

Control module kits are available both for 2-wire and 3-wire 
control with a wide range of control voltage inputs. Figure 4 
shows the components in 2-wire control module kit.  A 3-wire 
kit includes an additional single-pole auxiliary contact block.  
Refer to the 

Ordering Detail

 section for more information on 

control module kits and control voltages available.   

 

 
 
 

 

Figure 4 

 

4.2 Installation 

1.  Disconnect all power and mount the control module on the 

contactor as shown in Figure 1 (3-wire control type).  

2.  Mount the latch as shown in Figure 5. 
 

 

Figure 5 – 

Caution: Once latch cover has been installed, 

it may not be removed.  Ensure latch is properly installed 
prior to installing the latch cover. 

 

3.  Be sure the latch is firmly in place with the wire facing out 

and the slot positioned with tab inserted.   

4.  Mount the latch cover as shown in Figure 5. 

Caution: Once latch cover has been installed, it may not 
be removed.  Ensure latch is properly installed prior to 
installing the latch cover. 

5.  For 2-wire control, the auxiliary contact block is 

assembled to the right side of the base for “NC”.

  

 

6.  Operate contactor manually, using manual operation tabs 

(See Figure 5) on side, prior to installing cover to insure 
correct installation. 

 

IMPORTANT

:  Latch and electronic module must be used 

together to ensure proper operation.  Failure to do so will void 
warranty. 

 

4.3 Wiring 

Control module’s and auxiliary contact block’s terminals can 
accept a single wire from #22 to #12 AWG (either solid or 
stranded).   Maximum tightening torque required for the 
control module’s terminals is 5 in-lbs.   Auxiliary contact 
block terminals can accept parallel conductor size 
combinations utilizing torques identified in Table C. 

Latch 

Latch Cover 

Electrical 

Module 

Aux. 

Contact

Operation 

Tab

     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEH-41043

ECR LT#10001

Instruction Sheet                       Pub50765