I.L. 32-693 A
Page 9
Effective September 1998
Table 1 - Ground Fault Current Pickup Settings (Test Kit Display Amperes)
Installed
Rating Plug
Amperes (I
n
)
.25
.30
.35
.40
.50
.60
.75
1.0
100
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
200
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
250
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
300
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
400
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
600
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
800
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
1000
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
1200
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
1600
1.25
1.50
1.75
2.00
2.50
3.00
3.75
3.75
2000
1.25
1.50
1.75
2.00
2.50
3.00
3.00
3.00
2400
1.25
1.50
1.75
2.00
2.50
2.50
2.50
2.50
3200
1.25
1.50
1.75
2.00
2.00
2.00
2.00
2.00
4000
1.25
1.50
1.50
1.50
1.50
1.50
1.50
1.50
5000
1.20
1.20
1.20
1.20
1.20
1.20
1.20
1.20
Table 2 - Ground Fault Current Pickup Settings (Primary Amperes)
Installed
Rating Plug
Amperes (I
n
)
.25
.30
.35
.40
.50
.60
.75
1.0
100
25
30
35
40
50
60
75
100
200
50
60
70
80
100
120
150
200
250
63
75
88
100
125
150
188
250
300
75
90
105
120
150
180
225
300
400
100
120
140
160
200
240
300
400
600
150
180
210
240
300
360
450
600
800
200
240
280
320
400
480
600
800
1000
250
300
350
400
500
600
750
1000
1200
300
360
420
480
600
720
900
1200
1600
400
480
560
640
800
960
1200
1200
2000
500
600
700
800
1000
1200
1200
1200
2400
600
720
840
960
1200
1200
1200
1200
3200
800
960
1120
1200
1200
1200
1200
1200
4000
1000
1200
1200
1200
1200
1200
1200
1200
5000
1200
1200
1200
1200
1200
1200
1200
1200
(1)
For the Digitrip 1150, settings are non-discrete, and may fall between the values listed above. The corresponding pickup
values must then be calculated. (
I
g
x
I
n
, max 1200A)
(2)
Except as noted, tolerances on pickup levels are ± 10% of values shown in chart.
Pickup Setting (I
g
)
(1)
and Corresponding Pickup Levels (Secondary Amperes)
(2)
Pickup Setting (I
g
)
(1)
and Corresponding Pickup Levels (Secondary Amperes)
(2)