Specifications

Specification

Value

Power Supply

Models Ending 120SP: 120 VAC 

Models Ending 24USP: 24 VAC/DC, 40 V Max.

Output Signal

4-20 mA

Output Limit

23 mA

Response Time

100 ms (90% of Step Change)

Frequency Range

40-400 Hz

Accuracy

1% FS

Loading

500 ohms Max

Isolation Voltage

UL Listed to 1,270  AC, Tested to 5,000 VAC

Sensing Aperture

Solid Core Models: 0.75 in. (19 mm) dia. 

Split Core Models: 0.85 in. (21.7 mm) sq.

Housing

UL94 V0 Flammability Rated

Environmental

Operating Temperature: -4 to +122°F (-20 to +50°C)

Humidity: 0-95% RH, Non-Condensing

Approvals

None

Troubleshooting

Problem

Solution for Current  

Output Models

Sensor has no 

output

Power supply is not properly sized. Check power supply voltage 

and current rating.
Polarity is not properly matched. Check and correct wiring 

polarity.
For split core models, the core contact area may be dirty. Open 

the sensor and clean the contact area.

Output signal is 

too low

The range may be too high for the current being monitored. 

Select a difference EACP Series model with lower range.
The load current is not sinusoidal. Select an EACR Series sen-

sor that works on distorted waveforms.
Monitored current is below minimum required. Loop the 

monitored wire several times through the aperture until the 

“sensed” current rises above minimum. (‘Sensed Amps’ is 

equal to ‘Actual Amps’ multiplied by the ‘Number of Loops’).

Output signal is 

always at 20 mA

The range may be too low for the current being monitored. 

Select a different EACP Series sensor with a higher range.

Output signal is 

always at 4 mA

Monitored load is not AC or is not on. Check that the monitored 

load is AC and that it is actually on.

3

EATON 

www.eaton.com

 

Instructions Publication 

P51918

Effective July 2017

CurrentWatch™ EAC Series Current Sensors 

Powered AC Current Sensors, 120 VAC or 

24 VAC/DC, 4-20 mA Output