manualshive.com logo in svg
background image

P51921

 Rev 02

Effective: June 2007

Page 2

Questions? Call our Sensor Application Engineers at (800) 426-9184.

RANGES AND MAXIMUM AMPS

Housing

Range

Maximum Amps

Continuous

6 sec.

1 sec.

Solid Core

1.5-175A

150A

400A

1,000A

Split Core

2-200A

150A

400A

1,000A

SWITCHING DELAY

Delay Type

Low Range

Mid Range

High Range

On Delay

0.23 sec. max.

0.05 sec. max.

0.03 sec. max.

Off Delay

0.02 sec. max.

0.02 sec. max.

0.01 sec. max.

TROUBLESHOOTING

Problem

Solution

Switch is 
always tripped

The setpoint may be too low. Turn pot clock-wise to increase setpoint.

Switch may have been overloaded and contacts are burned out. Check the 
output load, remembering to include inrush on inductive loads (coils, motors).

Switch will 
not trip

The setpoint may be too high. Turn pot counter-clockwise to decrease 
setpoint.

For split core models, the core contact area may be dirty. Open the sensor 
and clean the contact area.

The monitored current may be below the minimum required. Loop the 
monitored wire several times through the aperture until the “sensed” current 
rises above the minimum. The sensed amps equals “actual amps” multiplied 
by the “number of loops.” Count loops on the inside of the aperture.

Switch may have been overloaded and contacts are burned out. Check the 
output load, remembering to include inrush on inductive loads (coils, motors).

SPECIFICATIONS

Specifi cation

Value

Power Supply

Self Powered–No Power Supply Needed

Output

Magnetically Isolated Solid State Switch

Output Rating

AC-Only Models: N.O./N.C. 1A @ 240V AC
AC/DC Models:
   N.O. 0.15A @ 240V AC/DC
   N.C. 0.20A @ 135V AC/DC

Off-State Leakage

ECSTD402SC and ECSTD405SP Models: 2.5 mA
All Other Models: Negligible

Response Time

Adjustable, 0.12 to 15 seconds

Setpoint Range

Solid Core Models: 1.5-12, 12-55 and 50-175A
Split Core Models: 2-12, 12-55 and 50-200A

Setpoint Adjustment

Solid Core Models: 15-Turn Potentiometer
Split Core Models: 4-Turn Potentiometer

Hysteresis

Constant 5% of Setpoint

Overload

See “Ranges and Maximum Amps” in Above Table

Isolation Voltage

UL Listed to 1,270V AC, Tested to 5,000V AC

Frequency Range

50-100Hz

Sensing Aperture

Solid Core Models: 0.75 in. (19mm) dia.
Split Core Models: 0.85 in. (21.7mm) sq.

Housing

UL94 V0 Flammability Rated

Environmental

Operating Temperature: -58 to +149° F (-50 to +65° C)
Humidity: 0-95% RH, Non-Condensing

Approvals

UL and ULC Listed (Pending)
CE Certifi ed (Pending)

394000109

SETPOINT ADJUSTMENT

The CurrentWatch™ ECSTD Series setpoint and time delay are adjusted 
through two four-turn pots (on split-core models) and 15-turn pots (on 
solid-core models). The unit comes from the factory with setpoint and 
time delay set to the lowest level (fully counter-clockwise). Turning the 
pots clockwise will increase their value. All pots have a slip-clutch to 
prevent damage at either end of their rotation. To determine where the 
adjustment is, turn the pot all the way counter-clockwise. This will return 
it to the minimum setpoint. 

Important Setpoint Adjustment Notes

•  Output contacts are solid-state. Check output status by applying 

the appropriate voltage to the contacts and reading the voltage 
drop across the contacts. An Ohmmeter set on “continuity” will 
give misleading results.

•  It is recommended the setpoint be adjusted to allow for the usual 

utility company voltage variations of 10 to 15 percent.

Typical Adjustment Steps

1.  Identify expected Input Range and position jumper accordingly. 

For LOW range, remove jumper entirely. For MID or HIGH range, 
place jumper over proper two pins.  

2.  Turn the setpoint pot to the minimum value (four turns for split-core 

models and fi fteen turns for solid-core models).

3.  Have normal operating current running through the switch. The 

output should be tripped because the pot is at its minimum 
setpoint. For units with LED, it should be fl ashing fast (two to three 
times per second). 

4.  Turn the pot clockwise until the unit un-trips. This is indicated by 

the slow fl ashing of the LED (once every two to three seconds), or 
by the changing of the output switch status.

5.  Now turn the pot counter-clockwise slowly until the unit trips again. 

a.  To set underload, turn the pot about 1/8 turn further counter-

clockwise

b.  To set overload, turn the pot about 1/8 turn further clockwise

6.  Adjust the time delay of the contact action in the same fashion. 

Increase time delay by turning the pot clockwise. For split-core 
models, each quarter-turn corresponds 

roughly

 to one second of 

delay time. Expect ten turns for a 15 second delay.

LED INDICATION / OUTPUT STATUS

Monitored Amps

Output

Smart-LED 
(If Present)

N.O.

N.C.

None or Minimum

Open

Closed

Off

Below Trip Level

Open

Closed

Slow (2 sec.)

Above Trip Level

Closed

Open

Fast (0.5 sec.)

WIRING DIAGRAM

Connect control or monitoring wires to the sensor. Use up to 14 AWG 
copper wire and tighten terminals to 5 inch-pounds torque. Be sure the 
output load does not 
exceed the solid state 
output rating. 

CAUTION! Incandescent 
lamps can have “cold 
fi lament inrush” current of 
up to ten times their rated 
amperage. Use caution 
when switching lamps.

HYSTERESIS

Setting

Hysteresis

Low

<

 

0.01A

Mid

<

 

0.1A

High

<

 

0.5A

AC or DC

Power

AC or DC

Load

Output Signal

To Monitored Load

Use caution when

switching lamps

Отзывы: