Figure 3
2. Re-install the back panel and tighten all eight (8) panel mounting screws
to 80 in-lbs (9.0 N-m).
3. To make final vertical adjustment, loosen the pivot bolts on the floodlight
yoke to position floodlight at the desired angle (limited to 60 degrees
forward and 45 degrees back, as shown in Figure 3).
4. Rotate the floodlight housing to the desired position.
5. Tighten the two 1/2”-13 bolts to 45 ft-lbs (61.0 N-m). Tighten the
5/16”-18 bolts in the adjustment slots to 12 ft-lbs (16.3 N-m).
6. Turn power on.
MAINTENANCE
•
Perform visual, electrical, and mechanical inspections on a regular
basis. The environment and frequency of use should determine this.
However, it is recommended that checks be made at least once a
year. We recommend an Electrical Preventive Maintenance Program
as described in the National Fire Protection Association Bulletin NFPA
70B: Recommended Practice for Electrical Equipment Maintenance
(www.nfpa.org).
•
The lens should be cleaned periodically to ensure continued lighting
performance. To clean, wipe the lens with a clean damp cloth. If this
is not sufficient, use a mild soap or a liquid cleaner. Do not use an
abrasive, strong alkaline, or acid cleaner. Damage may result.
•
Visually check for undue heating evidenced by discoloration of
wires or other components, damaged parts, or leakage evidenced
by water or corrosion in the interior. Replace all worn, damaged, or
malfunctioning components and clean gasket seals before putting the
luminaire back into service.
•
Electrically check to make sure that all connections are clean and
tight.
•
Mechanically check that all parts are properly assembled.
REPLACEMENT PARTS
Eaton’s Crouse-Hinds series Pro-Flood LED Floodlights are designed
to provide years of reliable lighting performance. However, should
the need for replacement parts arise, they are available through your
authorized Crouse-Hinds distributor. Assistance may also be obtained
through your local Crouse-Hinds representative or the Crouse-Hinds Sales
Service Department, P.O. Box 4999, Syracuse, New York 13221, Phone
866-764-5454.
DIMENSIONS
532.9
21.0
405.9
16.0
525.6
20.7
203.7
8.0
277
10.9
234.5
9.2
552.5
21.75
.55
120.7
4.75
IF 1684 • 04/22
Copyright © 2022, Eaton’s Crouse-Hinds Division Page 2
Figure 4
60°
45°
105°
45° PAST
VERTICAL
60° BEFORE
VERTICAL
AIMING RANGE
Units: (mm)
inches