Pro-Flood LED Floodlight

nPFM Series 25L Industrial LED Floodlight

Installation & Maintenance Information

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 1684

APPLICATION

Pro-Flood LED Floodlights construction is designed for use indoors and 

outdoors in marine and wet locations, where moisture, dirt, corrosion, 

vibration and rough usage may be present.

• IEC 60598-1 and IEC 60598-2-1

• Wet Locations

• IP66

Pro-Flood LED Floodlights are supplied for use with a choice of voltages:

• 100VAC – 277VAC, 50/60Hz and 108VDC – 250VDC

• 277VAC - 480VAC, 50/60Hz

WIRING

Wiring the Floodlight

1.  All components in the fixture are prewired so only line in, neutral, and 

ground need to be connected in the fixture to the terminals per the 

wiring diagrams using methods that comply with all applicable codes.  

Use supply cord with outer sheath diameter in accordance with Table 1. 

Terminate the equipment grounding conductor (green) first, the common 

(white) next, and finally, the line voltage (black) last. Secure all electrical 

connections and wiring entry glands.

Figure 1

LED CIRCUIT BOARD

+

-

LED CIRCUIT BOARD

+

-

NEUTRAL (WHT)

LINE IN (BLK)

LED CIRCUIT BOARD

+

-

LED CIRCUIT BOARD

+

-

HOUSING

GROUND (GRN)

DRIVER

INPUT

OUTPUT

LINE IN (BLK)
NEUTRAL (WHT)

V+ (RED)
V- (BLK)

GROUND (GRN)

DRIVER

INPUT

OUTPUT

LINE IN (BLK)
NEUTRAL (WHT)

V+ (RED)
V- (BLK)

GROUND (GRN)

GROUND TO

HOUSING

FILTER

TERMINAL

BLOCK OR

LEVER

LOCKS

Figure 2 - Wiring Diagram

Gland Name

PFM25L Ordering Suffix

Thread Type

Cable Diameter Range

 CAP816604

M20

M20 x 1.5

8.5 - 16.0 mm (0.34 - 0.62 in)

 CAP816794

M25

M25 x 1.5

8.5 - 16.0 mm (0.34 - 0.62 in)

Table 1

INSTALLATION

Mounting

  

YOKE MOUNT - POST MOUNT USING FLOODLIGHT YOKE ONLY

1.  Select a durable, corrosion resistant mounting surface capable of 

supporting the fixture’s 50 lb (22.7 kg) weight and cantilevered mass (as 

applicable).

2.  Using the floodlight yoke as a template, mark and drill desired location on 

mounting surface.

3.  Secure floodlight yoke to mounting surface by applying proper torque to 

corrosion resistant 1/2inch (12mm) bolts or lag screws accompanied by 

lock washers.

4.  Ensure that the safety chain is securely fastened between the yoke 

bracket and back cover.

IF 1684  •  04/22 

                      Copyright © 2022, Eaton’s Crouse-Hinds Division                                                                        Page 1

WARNING

To avoid potentially unsafe harm to eyes:

Mount at a minimum recommended height of 20ft (6m) - 7x6 optic,       

60ft - 3x3 optic.

Directive EU 2019/2022

This product contains a light source of energy efficiency class D or E.

To avoid the risk of fire, explosion, or electric shock,

 this product 

should be installed, inspected, and maintained by a qualified electrician 

only, in accordance with all applicable electrical codes.

WARNING

!

To avoid electric shock:

  Be certain electrical power is OFF before and during installation and 

maintenance.

To avoid burning hands: 

Make sure lens and housing are cool when performing maintenance.

WARNING

!

WARNING

To avoid potentially unsafe operating conditions:

Before opening, electrical power to the floodlight must be turned off.  

Keep tightly closed when in operation. 
Make sure the supply voltage is within the floodlight voltage range stated 

on the nameplate.
Do not operate in ambient temperatures above those indicated on the 

floodlight nameplate.
Use only replacement parts from Eaton’s Crouse-Hinds Business.
Use proper supply wiring as specified on the floodlight nameplate.
All gasket seals must be clean, and properly positioned.
Do not position the floodlight beyond the aiming range limits.
Do not exceed the maximum allowable current draw of 15 Amps when 

daisy chaining floodlights, (S886 configuration only).

!

!