Pro-Flood LED Floodlight
nPFM Series 25L Industrial LED Floodlight
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
IF 1684
APPLICATION
Pro-Flood LED Floodlights construction is designed for use indoors and
outdoors in marine and wet locations, where moisture, dirt, corrosion,
vibration and rough usage may be present.
• IEC 60598-1 and IEC 60598-2-1
• Wet Locations
• IP66
Pro-Flood LED Floodlights are supplied for use with a choice of voltages:
• 100VAC – 277VAC, 50/60Hz and 108VDC – 250VDC
• 277VAC - 480VAC, 50/60Hz
WIRING
Wiring the Floodlight
1. All components in the fixture are prewired so only line in, neutral, and
ground need to be connected in the fixture to the terminals per the
wiring diagrams using methods that comply with all applicable codes.
Use supply cord with outer sheath diameter in accordance with Table 1.
Terminate the equipment grounding conductor (green) first, the common
(white) next, and finally, the line voltage (black) last. Secure all electrical
connections and wiring entry glands.
Figure 1
LED CIRCUIT BOARD
+
-
LED CIRCUIT BOARD
+
-
NEUTRAL (WHT)
LINE IN (BLK)
LED CIRCUIT BOARD
+
-
LED CIRCUIT BOARD
+
-
HOUSING
GROUND (GRN)
DRIVER
INPUT
OUTPUT
LINE IN (BLK)
NEUTRAL (WHT)
V+ (RED)
V- (BLK)
GROUND (GRN)
DRIVER
INPUT
OUTPUT
LINE IN (BLK)
NEUTRAL (WHT)
V+ (RED)
V- (BLK)
GROUND (GRN)
GROUND TO
HOUSING
FILTER
TERMINAL
BLOCK OR
LEVER
LOCKS
Figure 2 - Wiring Diagram
Gland Name
PFM25L Ordering Suffix
Thread Type
Cable Diameter Range
CAP816604
M20
M20 x 1.5
8.5 - 16.0 mm (0.34 - 0.62 in)
CAP816794
M25
M25 x 1.5
8.5 - 16.0 mm (0.34 - 0.62 in)
Table 1
INSTALLATION
Mounting
YOKE MOUNT - POST MOUNT USING FLOODLIGHT YOKE ONLY
1. Select a durable, corrosion resistant mounting surface capable of
supporting the fixture’s 50 lb (22.7 kg) weight and cantilevered mass (as
applicable).
2. Using the floodlight yoke as a template, mark and drill desired location on
mounting surface.
3. Secure floodlight yoke to mounting surface by applying proper torque to
corrosion resistant 1/2inch (12mm) bolts or lag screws accompanied by
lock washers.
4. Ensure that the safety chain is securely fastened between the yoke
bracket and back cover.
IF 1684 • 04/22
Copyright © 2022, Eaton’s Crouse-Hinds Division Page 1
WARNING
To avoid potentially unsafe harm to eyes:
Mount at a minimum recommended height of 20ft (6m) - 7x6 optic,
60ft - 3x3 optic.
Directive EU 2019/2022
This product contains a light source of energy efficiency class D or E.
To avoid the risk of fire, explosion, or electric shock,
this product
should be installed, inspected, and maintained by a qualified electrician
only, in accordance with all applicable electrical codes.
WARNING
!
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance.
To avoid burning hands:
Make sure lens and housing are cool when performing maintenance.
WARNING
!
WARNING
To avoid potentially unsafe operating conditions:
Before opening, electrical power to the floodlight must be turned off.
Keep tightly closed when in operation.
Make sure the supply voltage is within the floodlight voltage range stated
on the nameplate.
Do not operate in ambient temperatures above those indicated on the
floodlight nameplate.
Use only replacement parts from Eaton’s Crouse-Hinds Business.
Use proper supply wiring as specified on the floodlight nameplate.
All gasket seals must be clean, and properly positioned.
Do not position the floodlight beyond the aiming range limits.
Do not exceed the maximum allowable current draw of 15 Amps when
daisy chaining floodlights, (S886 configuration only).
!
!