16
Replacement of Cover Gasket for Padmount Switchgear Side-Hinge-2 Models
Field Service inStructionS
MN285009EN April 2019
13. Apply touch-up paint to the cover bolts
13.1 Remove all items from the cover.
13.2 Clean the cover-bolt region all around the tank using
isopropyl alcohol on wipes.
13.3 Using the Bell Green aerosol can of trim paint, spray a
light coat to cover all cover bolt heads.
13.4 Allow enough time for the paint to be dry to the touch.
13.5 Spray a second thin coat of paint on all the cover bolt
heads.
13.6 Allow the paint to dry completely.
14. Reinstall the side cover Nut-Guards
14.1 Place the side cover Nut-Guards into position on both
sides of the main unit (Figure 72).
Figure 72.
14.2 Install fasteners on both upper corners of the face
plate (Figure 73).
Figure 73.
14.3 Replace the side-cover Nut-Guard fasteners on both
sides of main unit (Figure 74).
Figure 74.
15. If applicable: Reinstall the cable cabinets
15.1 Remove all obstacles between the cabinet assembly
and tank assembly.
15.2 Slide the cabinet assembly into position against the
main unit (from where you removed it in step 3).
15.3
For each side corner:
With a second person holding
the cabinet assembly, reinstall the three retaining clips
that connect the cabinet assembly to the main unit
(Figure 75).
WARNING
Tipping Hazard . Cabinet assembly is heavy in front .
Support the cabinet to guard against tipping while
the retaining clips are being removed .
Figure 75.