Production tests
Tests conducted in accordance with IEEE Std 386™-2006 standard:
•
ac 60 Hz 1 Minute Withstand
•
50 kV
•
Minimum Corona Voltage Level
•
26 kV
Tests conducted in accordance with Eaton re quire ments:
•
Physical Inspection
•
Periodic Fluoroscopic Analysis
Ordering information
To order a 35 kV Class Stand off Bushing Kit for PUSH-OP refer to
Table 2.
Each kit contains:
•
Standoff Bushing with Bracket
•
Shipping Cap (not for energized operation)
•
Silicone Lubricant
•
Installation Instruction Sheet
Table 1. Voltage Ratings and Characteristics – Insulated
Standoff Bushing
Description
kV
Standard Voltage Class
35
Maximum Rating Phase-to-Ground
21.1
ac 60 Hz 1 Minute Withstand
50
dc 15 Minute Withstand
103
BIL and Full Wave Crest
150
Minimum Corona Voltage Level
26
Voltage ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.
Table 2. Standoff Bushing Kit
Description
Catalog Number
Insulated Standoff Bushing
PISB635
Insulated Standoff Bushing with hitch pin
PISB635HP
3
Catalog Data
CA650049EN
Effective May 2015
600 A 35 kV class PUSH-OP insulated standoff bushing
www.eaton.com/cooperpowerseries