background image

Production tests

Tests conducted in accordance with IEEE Std 386™-2006 standard:

• 

ac 60 Hz 1 Minute Withstand 

• 

50 kV

• 

Minimum Corona Voltage Level 

• 

26 kV

Tests conducted in accordance with Eaton re quire ments:

• 

Physical Inspection

• 

Periodic Fluoroscopic Analysis

Ordering information

To order a 35 kV Class Stand off Bushing Kit for PUSH-OP refer to 

Table 2.

Each kit contains:

• 

Standoff Bushing with Bracket

• 

Shipping Cap (not for energized operation)

• 

Silicone Lubricant

• 

Installation Instruction Sheet

Table 1.  Voltage Ratings and Characteristics – Insulated 

Standoff Bushing

Description

kV

Standard Voltage Class

35 

Maximum Rating Phase-to-Ground

21.1 

ac 60 Hz 1 Minute Withstand

50

dc 15 Minute Withstand

103

BIL and Full Wave Crest

150

Minimum Corona Voltage Level

26

Voltage ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.

Table 2.  Standoff Bushing Kit

Description

Catalog Number

Insulated Standoff Bushing

PISB635

Insulated Standoff Bushing with hitch pin

PISB635HP

3

Catalog Data 

CA650049EN

Effective May 2015

600 A 35 kV class PUSH-OP insulated standoff bushing

 www.eaton.com/cooperpowerseries

Отзывы: