Wiring the Transformer

www.eaton.com/lightingsystems

High Voltage  

Compartment

Low Voltage  

Compartment

Conduit Knockout 
for Piping

Conduit Knockout 
for Piping

Conduit Knockout 

 for Piping

Wiring the Transformer

The transformer provides power to the Relay Stack 

Controller (RSC) and to the ControlKeeper T logic board. The 

transformer is multi-tapped and voltages are color coded. 

The transformer is available in 120V, 277V, 347V 60 Hz or 

220V, 230V, 240V 50/60 Hz models. It is recommended that 

a dedicated branch circuit with circuit protection be provided 

for the transformer.
1.  Connect the solid black wire to the dedicated branch 

circuit that is powering the transformer.

2.  Connect neutral wire to the wire with the appropriate 

color coding for the voltage being used.

 

See chart below for clarification.

Tablt 1.  TransfNrmtr CNlNr Charo

Line Voltage

Black

120 VAC

White/Black

277 VAC

White/Orange

347 VAC

Brown

220 VAC 50/60 Hz

White/Red

230 VAC 50/60 Hz

White/Blue

240 VAC 50/60 Hz

White/Blue

Connecting Relay Loads

The relay cards will be pre-mounted by the manufacturer 

in the enclosure per the order specifications.There are 

currently three available relay types for the ControlKeeper 

T enclosure. This includes the Serial Standard Relay Card, 

the Serial Two Pole Relay Card and the Serial Latching Relay 

Card. Please refer to the specific section for your relay card 

type that you are wiring. For all relay types:
1.  Verify that all wire cuttings are removed from the 

enclosure.

2.  Take the protective shrink-wrap off of the relay cards 

once the wire cuttings are removed from the enclosure.

3.  Test branch circuits for short circuits prior to landing 

wiring on relays.

Note:

N

Neutrals terminate within the adjoining lighting panel.

Standard Relay Card Notes

1.  The Standard Relay Card is rated for single-pole load 

use only. Connection of 2 pole circuits/loads to the 

Standard Relay Card will void the equipment warranty 

and may result in severe injury or death, and/or damage 

to the equipment.

2.  Relay ratings are 120 or 277 volt, 20 amp maximum. 

Standard relays are available in a Normally Open 

configuration.

3.  Relay terminal blocks have a maximum limit of 10 AWG 

wire.

Standard Relay Card Wiring

The standard relay is a simple contact closure, breaking the 

line and load wires of a normal circuit. To wire the relay into 

the control circuit:
1.  Connect a 120 or 277 volt, 20 amp max, de-energized 

branch circuit breaker to the relay terminal block 

position labeled LINE.

2.  Connect the load wiring to the output terminal block 

position labeled LOAD.

3.  Tighten down relay terminal screws. Manufacturer’s 

recommended torque rating is 7 lbs-in. (0.59 lbs-foot) 

(0.8 Nm).

4.  Document relay to circuit information for future 

reference.

Содержание CKT16

Страница 1: ...safety procedures could result in severe injury or death and or damage to the equipment 8 Document all wiring that is terminated to the relays so that the lighting control equipment can be properly co...

Страница 2: ...Two Pole Relay Card and the Serial Latching Relay Card Please refer to the specific section for your relay card type that you are wiring For all relay types 1 Verify that all wire cuttings are remove...

Страница 3: ...down relay terminal screws Manufacturer s recommended torque rating is 18 lb in 1 475 foot lbs 2 0 Nm 4 Document relay to circuit information for future reference To Lighting Load From Branch Circuit...

Страница 4: ...ay result in it breaking Manually Controlling Relays The relays in the ControlKeeper T enclosure may be controlled before the logic board is in place using the Relay Stack Controller or the individual...

Страница 5: ...ge wiring must enter the cabinet from the lower left side of the enclosure or be piped through the high voltage section in conduit using the special knockouts reserved for this section 3 All low volta...

Страница 6: ...gateway called the GDS I GDS stations are wired using the Eaton s Cooper LCCP or LCCNP cable or Belden 1502P or 1502R equivallents See the ControlKeeper T logic board installation instructions for fur...

Страница 7: ...de des vis 1 4 incluses Pour obtenir le fonctionnement correct des vis vous devez les pousser d licatement et effectuer de tour vers la gauche jusqu ce que la t te de la vis soit dans la position hori...

Страница 8: ...r usage avec une charge un seul p le Le branchement des deux circuits charges bipolaires la carte de relais standard annulera la garantie de l quipement et peut entra ner des blessures s rieuses ou la...

Страница 9: ...informations concernant le branchement du relais au circuit pour une r f rence ult rieure C blage des relais C ble 6 AWG max Classification du relais 20A 208 240 480V Vers la charge d clairage 1 Vers...

Страница 10: ...ur neutralise le relais qui attend alors la prochaine commande en provenance du ControlKeeper L interrupteur basculant trois positions du RSC permet de neutraliser l interrupteur prioritaire de relais...

Страница 11: ...le c blage basse tension doit tre achemin dans un tuyau s par du c blage de tension de ligne 4 Utilisez un c ble 18 AWG torsad sans isolant pour tout c blage de dispositif de fermeture basse tension...

Страница 12: ...Keeper T pour en savoir plus au sujet de cette mise terre Mise terre de la carte logique Conformit UL 924 Avec l ajout de l accessoire du module de relais interface le syst me de contr le d clairage a...

Страница 13: ...nfigurar correctamente el equipo de control de iluminaci n y poder programarlo para su funcionamiento Montaje del alojamiento 1 Si se est utilizando un alojamiento de tama o 32 o 48 extraiga la placa...

Страница 14: ...te la pel cula protectora termorretr ctil de las tarjetas de rel luego de haber quitado los fragmentos de cables del alojamiento 3 Pruebe los circuitos de rama para corroborar que no se produzcan cort...

Страница 15: ...as caracter sticas nominales del rel de dos polos son de 208 240 y 480 voltios y 20 amperios como m ximo 2 Los bloques de terminales del rel tienen un l mite m ximo de cable de 6 AWG 3 Los rel s de do...

Страница 16: ...cada rel Controlador del bloque del rel El Controlador del bloque del rel RSC se encuentra en la parte inferior del alojamiento Funciona como un dispositivo de anulaci n maestro en el sistema El RSC...

Страница 17: ...lmente reservados para esa secci n 3 Todos los cables de bajo voltaje deben pasarse por el conducto separado de los cables de voltaje de l nea 4 Pruebe todos los cables de la red para verificar que no...

Страница 18: ...T a trav s de una puerta de enlace llamada GDS I Las estaciones GDS se cablean por medio del cable Eaton s Cooper LCCP o LCCNP o de sus equivalentes Belden 1502P o 1502R Consulte las instrucciones de...

Страница 19: ......

Страница 20: ...b www coopercontrol com para conocer nuestros t rminos y condiciones 2018 Eaton All Rights Reserved Printed in USA Publication No IL503028EN March 1 2018 Eaton 1121 Highway 74 South Peachtree City GA...

Отзывы: