Eaton BladeUPS DoS Installation Instructions P-164000613—Rev 3
21
Section 10 Specifications
This chapter provides the following specifications:
l
Model list
l
Weights and dimensions
l
Electrical input and output
l
Environmental and safety
l
Battery
Table 3. Model List
UPS Model Number
Power Levels
(Rated at Nominal Inputs)
xxx
12 kVA or 12 kW at 208V
See Note
EBM Model Number
BladeUPS EBM
NOTE
Derated for line cord and nominal line voltage
Cord Model Number
Description
Input Plug Type
Length
UPSCordPUL
12 kW UL input/output
Anderson
See Note
0.5m (1.5 ft)
NOTE
Customized Anderson connector for use with Eaton Dual BladeUPS
Table 4. Weights and Dimensions
UPS
Extended Battery Module
(EBM)
Dimensions
(W
D
H)
12" x 33" x 46"
438
660
131 mm
17.2”
26.0”
5.2” (3U)
Weights
See Note
Blade UPS model without internal batteries: 60.35kg (133.05lb)
Individual battery: 2 kg (4.4 lb)
Each battery tray: 20 kg (44 lb)
Blade UPS electronics module: 19.5 kg (43 lb)
Blade UPS bypass sel switch: 11.06kg (24.38lb)
77 kg (170 lb)
Table 5. Electrical Input
xxx Model
xxx Model
Nominal Voltage
120/208V three-phase
230/400V three-phase
Nominal Frequency
50/60 Hz
50/60 Hz
Frequency Range
45–65 Hz
45–65 Hz
Default Frequency
Auto-detected
Auto-detected
Rated Input Current
36A
24A
Connections
IEC 309-60A power cord
IEC 309-32A power cord
For paralleling, a single Anderson input/output cord connects to the
BladeUPS Bar (see Table 3 on page 21).