Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
77..88
TTeessttiinngg N
Neew
w B
Baatttteerriieess
NOTE 1
The batteries must be fully charged and the UPS must not be in Battery mode to
perform the battery test.
NOTE 2
For an accurate battery test, test the UPS with at least 10% load applied to the UPS.
To test new batteries:
1.
Plug the UPS into a power outlet for 48 hours to charge the battery.
2.
Press any button to activate the menu options.
3.
Select CONTROL then START BATTERY TEST.
NOTE
The battery test may not start immediately. The request is scheduled and the UPS
determines when the test starts.
During the battery test, the front panel displays “Battery Test Pending.”
A failed battery test initiates a Battery Test Failed alarm.
To cancel a battery test in progress:
1.
Press any button to activate the menu options.
2.
Select CONTROL, START BATTERY TEST, then CANCEL.
77..99
R
Reeppllaacciinngg tthhee EElleeccttrroonniiccss M
Moodduullee
You can easily replace the electronics module without turning the UPS off or disconnecting the load. Battery
mode is not available and your equipment is not protected; however, the utility power continues to be filtered
passively by the UPS.
If you prefer to remove input power to change the electronics module, see section
”Standalone UPS
Shutdown”.
NOTE
DO NOT DISCONNECT the electronics module while the UPS is in Battery mode.
To replace the electronics module:
1.
Standalone UPS configurations only.
Transfer the UPS to Bypass mode. Continue to Step 3.
Parallel for capacity configurations only.
Transfer the UPS to Bypass mode. The CAN bus remains
energized.
Parallel for redundancy configurations only.
No mode transfer is necessary. If the UPS is operating in a
parallel for redundancy configuration when its electronics module is removed, the load automatically
transfers to the remaining UPSs. The CAN bus remains energized.
NOTE
In single unit and capacity parallel systems, disconnecting the control panel from the
electronics module automatically transfers the UPS to Bypass mode. However,
transferring the UPS to Bypass mode manually BEFORE disconnecting the control panel
provides extra protection to the electronics module and is recommended.
2.
Parallel configurations only.
Disconnect the redundant signal cable(s) from the UPS. For the location of
the redundant signal cable, see
.
3.
Remove the UPS front cover and the electronics module and set them aside (see
):
Содержание BladeUPS none
Страница 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Страница 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Страница 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Страница 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Страница 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Страница 160: ...16420164914 164201649 14 ...