background image

For more information visit: www.eaton.com

IIB01602019E

Instructional Booklet

Page

10

Effective: March 2010

O&M Manual for the Eaton ATC-100

Automatic Transfer Switch Controller

2.3.1  Programming Jumpers

The ATC-100 is programmable via the jumpers on the back of the 

unit.  The jumper selections are discussed in Section 5, Program-

ming.

2.3.2  Reset Pushbutton

The ATC-100 has a Reset pushbutton in the top right corner to 

reset the following alarm conditions:

“Utility Connected” LED is blinking;

“Generator Connected” LED is blinking; and

“Generator Available” LED is blinking.

See Section 5.2, ATC-100 Troubleshooting for further information 

on these alarm conditions.

Note: 

Pressing the Reset pushbutton will also clear the Generator Test pro-

gramming.  It will be necessary to set up the Generator Test again after 

pressing the Reset pushbutton.

2.4  Control Inputs

The ATC-100 has two individual control input signals that are 

used to sense transfer switch position.  The inputs require and 

external contact closure to the DC_Output pin (J4, Pin1). The 

DC_Output pin is connected internally to the unregulated DC sup-

ply (26 V) and appropriate current-limiting to provide a nominal 

current of 10 mA per channel.

2.4.1  Control Input Descriptions

The Control Input “State” definitions are as follows.

Connected - 

When the input is shorted by an external contact or 

connection.

Unconnected - 

When the input is NOT shorted by an external con-

tact or connection.
The Control Input operations are defined as follows.

Utility Closed

When this input (J4, Pin 2) is in the “Connected” state, it indi-

cates to the ATC-100 that the utility switching device is closed.  

When this input is in the “Unconnected” state, it indicates to the 

ATC-100 that the utility switching device is open.  This input is 

typically wired to the utility device auxiliary contact that is closed 

when the utility switching device is closed. 

Generator Closed

When this input (J4, Pin 3) is in the “Connected” state, it indi-

cates to the ATC-100 that the generator switching device is 

closed.  When this input is in the “Unconnected” state, it indicates 

to the ATC-100 that the generator switching device is open.  This 

input is typically wired to the generator device auxiliary contact 

that is closed when the generator switching device is closed.

2.5  Output Relays

The primary control outputs of the ATC-100 are dry relay con-

tacts.  These relays are comprised of one latching “Form C” relay 

to provide the generator start contacts, and two conventional coil 

“Form C” relays (that implement only the Form A contact) neces-

sary to complete the electrical control function.  Since the outputs 

were tested per the UL 1008 Dielectric Test and the IEC 947-6 

Dielectric Test, the dielectric rating for each output is a minimum 

of 1500 Vac.  
The Output Relay functions are divided into two categories:

Customer Connections and

Transfer Operation Connections.

Figure 4. J-4 and J-5 Connector Connections.

2.5.1 Customer Connections

Generator Start Relay

The generator start relay is a latching relay with Form C contacts 

of silver alloy with gold flashing for closure of the generator start 

circuit.
The Form C contact is implemented with the Common Pin (J-5, 

Pin 2), the Normally Open Pin (J-5, Pin 1) and the Normally Closed 

Pin (J-5, Pin 3) (see Figure 4).  The generator start relay contacts 

are rated for 5 A, 1/6 HP @ 250 Vac.  The DC rating is 5 A @ 30 

Vdc with a 150 W maximum load.

Note: 

Note:The ATC-100 MUST BE properly grounded at J-4, Pin 8 for 

proper operation.

2.5.2  Transfer Operations Connections

The K1 and K2 relays are factory wired to operate the transfer 

switch.  The relay contacts for each are rated for 10 A, 

1/3 HP @ 250 Vac.  The DC rating is 10 A @ 30 Vdc.

Output Relay K1

This relay is used to control transfer switch position.  Only the 

Form A contact is available for connection.
This output is used to close the utility switching device.  The K1 

relay momentarily energizes until the ATC-100 senses that the 

utility switching device is closed, then K1 de-energizes.  The K1 

outputs are the Common Pin (J-4, Pin 4) and Normally Open Pin 

(J-4, Pin 5) (see Figure 4).

CONNECTOR J4

CONNECTOR J5

Содержание ATC-100

Страница 1: ...M Manual for the Eaton ATC 100 Automatic Transfer Switch Controller Instructional Booklet Description Page 1 Introduction 2 2 Hardware Description 5 3 Operation 11 4 Programming 13 5 Troubleshooting...

Страница 2: ...the utility power source In Automatic Transfer Switch ATS equipment the switch s intel ligence system initiates the transfer when the utility power falls below or rises above a preset voltage or freq...

Страница 3: ...ity is defined as failed when it is outside of its undervoltage set point range for the nominal voltage setting Generator Failed or Fails Generator is defined as failed when it is outside of its under...

Страница 4: ...wer Source Annunciation This feature provides LED s to indicate switch position and power source availability indications Switch Position Provides LED s to indicate the transfer switch position 12C Ut...

Страница 5: ...er will determine if In phase transition is performed In phase transition is attempted for 10 minutes on a 3 phase sys tem If unsuccessful an open transition is performed Time Delay Neutral TDN featur...

Страница 6: ...ooklet Page 6 Effective March 2010 O M Manual for the Eaton ATC 100 Automatic Transfer Switch Controller Figure 1 The ATC 100 Front Panel UTILITY CONNECTED UNIT STATUS GENERATOR CONNECTED SET GENERATO...

Страница 7: ...is running the test will terminate Set Generator Test Pushbutton The Set Generator Test pushbutton allows the user to test the generator automatically on a periodic every 7 14 or 28 days basis Pressin...

Страница 8: ...se B Phase A Generator Phase C Phase B Phase A Generator Utility Utility Generator Control Power Generator K1 Com K1 NO DC_Output Generator Closed K2 Com K2 NO Earth Ground Gen Start Com Gen Start NO...

Страница 9: ...Generator Phase C Phase B Phase A Generator Utility Utility Generator Control Power Generator K1 Com K1 NO DC_Output Generator Closed K2 Com K2 NO Earth Ground Gen Start Com Gen Start NO Control Inpu...

Страница 10: ...e it indi cates to the ATC 100 that the generator switching device is closed When this input is in the Unconnected state it indicates to the ATC 100 that the generator switching device is open This in...

Страница 11: ...gize which closes its Normally Open contacts and opens its Normally Closed contacts When the generator source meets the requirements to be consid ered available the Time Delay Normal to Emergency TDNE...

Страница 12: ...n 90 seconds of the ATC 100 providing the generator start command 3 If during the TDNE countdown the generator source goes unavailable more than three times TDNE will restart each time 4 If the genera...

Страница 13: ...volts As ordered Jumper selectable Three phase or single phase 1 or 3 As ordered Jumper selectable Utility Undervoltage Dropout 80 of Nominal Voltage 80 of Nominal Voltage Fixed setting Generator Und...

Страница 14: ...n when it was commanded to open within 6 seconds Generator switching device did not close when it was commanded to close within 6 seconds Generator closed contacts did not open when Generator switchin...

Страница 15: ...the plug type connec tors Step 5 Remove the four 4 mounting screws located on the four corners that hold the unit and trim plate against the door or panel These are accessed from the front of the unit...

Страница 16: ...System Test Generator Test TDES timer times out Send generator start signal Energize Gen Start relay TDNE timer times out Open Utility breaker Momentarily energize K2 Y Generator is powering the load...

Страница 17: ...times out Send Engine Start signal Energize Gen Start relay Is Generator Available TDNE timer times out Sync timer times out Open Utility Switching Device and Close Generator Switching Device Momentar...

Страница 18: ...No Yes Sync timer times out Open Generator Switching Device Momentarily energize K1 Sources synchronized before Sync timer times out No Yes and Close Utility Switching Device Utility is powering the l...

Страница 19: ...IB01602019E For more information visit www eaton com Instructional Booklet Effective March 2010 Page 19 O M Manual for the Eaton ATC 100 Automatic Transfer Switch Controller Notes...

Страница 20: ...RE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence strict liabi...

Отзывы: