manualshive.com logo in svg
background image

Page 2 

Functional Description 

An 

E

aton AQB-L400 Adapter Kit provides the means for 

converting the normally male configured pri­mary 

connections of an AQB-L400/LL400 current limiting 

circuit breaker to female configured primary connections, 

normally associated with an AQB-LF400 circuit breaker 

(Figure 1-5). A close out plate, attached directly to the 

front of the AQB-L400 circuit breaker with four mounting 

screws, provides the deadfront cover required to com­

plete the conversion. 

The adapter kit itself is comprised of line and load side 

adapter blocks, six female spring loaded primary connec­

tion adapters, a close out plate, and four mounting 

screws (Figure 1-3). 

PART 2. INSTALLATION/OPERATION 

a. Turn off all power.

b. Remove LF400 breaker, if applicable.

c. The standard male type slip connectors shall be

removed from the AQB-L400/LL400 circuit breaker.

The threaded end of the female connection adapters

attaches in their place. The other end of the female

connection adapters provides the female slip con­

nections required for the AQB-LF400 configuration.

d. Mount the tulips to the line and load ends.

1. Note that 4 tulips are offset mounted on their

pads and 2 tulips are centered (Figure 1-4).

2. The centered tulip assemblies mount to the cen­

ter pole.

3. Offset tulip assemblies mount to the left and right

poles,  with the tulips oriented to the outside of

the breaker.

4. Before tightening the hardware, check the align­

ment using the adapter block as a template.

5. If the alignment is correct, tighten the hardware.

I.L. 15578A

A

CAUTION 

TO PROPERLY REMOVE THE ADAPTED AQB-L400/ 

LL400 CIRCUIT BREAKER, UNSCREW THE BOLTS 

LOCATED IN THE ADAP TER BLOCK, NOT THE 

BREAKER MOUNTING BOLTS LOCATED IN THE 

BREAKER FRAME. 

e. The adapter block is mounted to the circuit breaker 

using breaker mounting bolts.

f. The modified breaker is mounted to the LF400 

mounting blocks using hardware supplied with the 

adapter block.

g. After mounting the breaker on the LF400 block, 

attach the close out plate to the front. Once attached 

to the front of the AQB-L400/LL400 circuit breaker 

with four mounting screws, the close out plate 

insures a deadfront installation.  In addition, the close 

out plate provides front access to the circuit breaker's 

operating handle, trip unit adjustments, lower breaker 

mounting bolts and megger holes. Access to the 

adapter block mounting bolts, however, requires 

removal of the close out plate.

h. Since the 

E

aton Adapter Kit applied to an AQBL400/

LL400 breaker is a direct replacement for an already 

installed AQB-LF400 breaker, modifica­tions to the 

existing bus mounting system are not required. An 

already adapted AQB-L400/LL400 breaker can be 

mounted on existing blocks, and secured in place 

with the provided upper and lower adapter block 

bolts (Figure 1-6). 

Fig.  1-4.  Closeup of Tulips Showing Center and Offset 

Mountings 

Effective October 1997 

I.L. 15578A

Fig.  1-5.  Rear View of Navy Type AQB-L400 Circuit 

Breaker and Adapter Kit Combination Display­

ing Female Configured Primary Connections 

Effective October 1997 

Page3 

Fig.  1-6.  Navy Type AQB-L400 Circuit Breaker and 

Adapter Kit Combination Plugged Into Male 

Mounting Blocks 

In general, follow the mounting procedures normally used 

for mounting any AQB-LF400 circuit breaker, when 

installing the AQB-L400/LL400 circuit breaker and 

Adapter Kit combination. Follow the instructions and pro­

cedures provided with the AQB-L400/LL400 circuit 

breaker when operating the AQBL400/LL400 and 

Adapter Kit combination.  Refer to Technical Manual 

1240C33H01 

PART 3. REPLACEABLE PARTS 

a. L400/LL400 plus Adapter Kit: See 

E

aton

b. Adapter Kit: 6590C82G01

c. LF400 Mounting Block: 6590C82G03 

Отзывы: