manualshive.com logo in svg
background image

Effective May 2011
Supersedes April 1988

Instruction Leaflet 

IL15465

Instructions for A200 Size 3 or 4, 3 Pole

Motor Controller

THE CONTACTORS

The A200 motor controller, when wired as shown in Figures 

5 and 6, will operate as a full voltage starter and will give 

protection against overload, but not against short-circuit currents, 

when wired and provided with overload relay (OLR) heaters as 

listed in heater selection tables or when used with any means of 

inherent protection activated by motor temperature.

The controller should be protected against short circuits by 

providing branch circuit protection not to exceed the maximum 

protective device ratings listed in Table I. 

This industrial type control is designed to be installed, oper-

ated, and maintained by adequately trained workmen. These 

instructions do not cover all details, variations, or combinations of 

the equipment, its storage, delivery, installation, check out, safe 

operation, or maintenance. Care must be exercised to comply with 

local, state, and national regulations, as well as safety practices, 

for this class of equipment.

AUXILIARY CONTACTS - TYPE J

A J20 with two normally-open poles is supplied mounted in the 

upper left hand corner recess of the contactor. One pole is used 

as the holding circuit auxiliary.

Отзывы: