4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10
61
6.
Replace the front covers and continue to “
UPS Startup Without an External Bypass Switch
,
Startup for Units Installed with an Eaton BPM Bypass Switch
or
Startup for Units installed with a BPE Type Switch
”.
66..22
U
UP
PS
S S
Sttaarrttuupp W
Wiitthhoouutt aann EExxtteerrnnaall B
Byyppaassss S
Sw
wiittcchh
To start the UPS unit for the first time after installation:
1.
If external battery cabinets (EBMs) are installed, check the cable connections between the UPS and
external battery cabinets (see , “
Standard Battery Cabinet Installation
or
”).
2.
Ensure that all power modules and battery modules are properly installed into the UPS cabinet.
3.
If you are using power management software, connect your computer to either the DB9 or USB
communication ports on the top rear panel using the supplied communication cables.
Figure 55. Communication Ports
USB Port
(CN12)
DB9 Port
(CN17)
4.
When starting the UPS, apply input power to the UPS by closing the service circuit breaker:
•
If external battery cabinets are installed, close the DC emergency disconnect switch button on the
back of each external battery cabinet. Insert the switch key supplied with the cabinet into the button
and turn clockwise 1/2-turn. Pull the button out to close the switch. Turn the key back counter-
clockwise, and remove the key.
5.
The UPS control panel display automatically turns on whenever input power is present and at least one
power module is installed (see , “
”).
6.
Set up the initial operating parameters through the control panel display (see “
” ).
7.
If applicable, test proper operation of optional external control signals and computer communication before
connecting the load. (See “
” for details.)
8.
If there are receptacles on the UPS rear panel, plug the equipment to be protected into the UPS output
receptacles.
NOTE
DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.
9.
Turn on the equipment that is connected to the UPS.
10. If there is an external bypass switch, ensure a proper phase check has been completed then turn the
switch to UPS. Otherwise, close the load distribution circuit breaker(s).
Содержание 9PXM8S4K
Страница 1: ...p n P 164000669 Revision 10 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS...
Страница 4: ......
Страница 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Table of Contents...
Страница 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 List of Tables...
Страница 20: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Physical Features...
Страница 54: ...42 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 System Wiring Diagram...
Страница 98: ...86 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Display Menu Screens...
Страница 104: ...92 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Communication Slots...
Страница 114: ...102 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Receptacle Circuit Breaker Ratings...
Страница 119: ...4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 107 Two Year Limited Warranty...
Страница 120: ...P 16400066910 P 164000669 10...